Removing and Installing the Controller Chassis
PAGASYS GEN II (P-SYS-G)
Federal Signal www.fedsig.com
11. Plug the cables from the Access Panels or Access Panel Aggregator card into the
RJ45 jack sockets located on the card installed in the AP Mux slot 1.
12. Plug the RJ45 cables from the amplifiers into the input/output RJ45 jack sockets
located on the top of the Amplifier Audio Mux.
13. Plug the fireman’s microphone into the fireman’s microphone socket, if available.
Figure 43 Connections
14. Write down or photograph the labels and connector positions of all the cables
exposed by the removed front cover.
5.3 Removing and Installing the Amplifier Chassis (From Cabinet)
5.3.1 Safety Instructions
This equipment is part of a Voice Alarm System and there is the possibility of
dangerous voltages being present in the main equipment rack.
Internal servicing must be performed by a competent, qualified engineer.
5.3.2 Recommendation for the Equipment Location
Avoid locating the equipment:
• Near heat sources
• In direct sunlight
• Where it is exposed to high humidity or dust levels