Error screens
Pressing the
or
key during Write operation aborts the
operation under way and displays this error.
Updating of the
function code data in the inverter is incomplete, with some of it
remaining old. Do not run the inverter in this state. Before
running the inverter, redo the writing or perform initialization.
For safety considerations, the following situations are treated
as an error:
•
No valid data is found in the keypad’s memory. (No Read
operation has been performed since factory shipment; or, a
Read operation has been cancelled or aborted.)
•
The data held in the keypad’s memory has an error.
•
There is a mismatch in inverter’s model number.
•
A Write operation has been performed while the inverter is
running.
•
The inverter is data-protected.
The function code data held in the keypad is incompatible with
that in the inverter. (Either data may be non-standard or a
version upgrade performed in the past may have made the
keypad or inverter incompatible. Contact your Fuji Electric
representative.)
Figure 3.20 Screen Transition for "WRITE" (continued)
If an ERROR screen or ERROR Ver. screen appears, press the
key. When Reset is complete, the
screen will go back to List of data copy operations.
If an ERROR Ver. screen appears:
To stop Write operation, press the
key. When Reset is complete, the screen will go back to List of
data copy operations.
To proceed to Write operation, press the
key. After completion of Write operation, be sure to
perform Verify operation to check all of the unwritten functions codes and take necessary measures.