3.4.9 Data copying
-- Menu #8 "Data Copying" --
Menu #8 "Data Copying" in Programming mode allows you to read function code data out of an inverter for
which function codes are already set up and then to write such function code data altogether into another
inverter, or to verify the function code data held in the keypad with the one in the inverter.
The keypad can hold three sets of function code data in three areas of its internal memory so that it can be used
with three different inverters. You can read the function code data of an inverter into one of these memory areas
or write the function code data held in one of these memory areas into the inverter you select. On the LCD
screen, each set of function code data or memory area is given a name such as DATA 1 and DATA 2.
Basic key operation
(1) When the inverter is powered on, it automatically enters Running mode. In Running mode, press t e
h
key to enter Programming mode. The menu for function selection will appear.
(2) Use the
/
keys to move the pointer
Æ
to "8. DATA COPY."
(3) Press the
key to call up the data copy index screen (list of data copy operations).
(4) Use the
/
keys to select the target operation (read, write, verify, or check).
(5) Press the
key to establish the selected operation and then select data stored in the keypad.
(6) Press the
key to establish the selection and perform the operation of your choice (for details, refer to the
LCD screen transition diagram below).
(7) Press the
key to return to the menu.
Figure 3.18 shows the LCD screen transition for "8. DATA COPY."
1) Selecting Copy Operation
List of data copy operations
Select desired operation by moving the cursor with
/
keys.
To return to Menu, press the
key.
Figure 3.18 Screen Transition for "8. DATA COPY"
Table 3.12 List of DATA COPY Operations
Operation Description
Read: Read data
Reads out function code data from the inverter and stores it into the internal memory of
the keypad.
Write: Write data
Writes the data held in the selected memory area of the keypad into the inverter.
Verify: Verify data
Verifies the data held in the keypad’s internal memory against the function code data in
the inverter.
Check: Check data
Checks the model information (format) and function code data held in the three memory
areas of the keypad.
Select the target menu by moving the pointer
Æ
with
/
keys.
Press
key to establish the target menu.
/
3-28