- 34 -
INF-TN1FSH-E
(10) Adjust the position by aligning the match mark of
the absorber unit and the sensor unit with the
marking line.
(11) After mounting the sensor on the upstream side
(along with the absorber unit in the case of metal
piping), mount the sensor on the downstream side
(along with the absorber unit in the case of metal
piping) in the same manner.
(12)
Connect the temperature sensor cable to the
waterproof connector for the temperature sensor
cable.
(13) Connect the ultrasonic signal cable to the BNC
connector of the sensor unit, being careful not to
reverse the wiring on upstream and downstream
sides.
Note:
Do not pull the cable at this time. Otherwise the sensor
unit may move, thus causing problems in measurement.
Downstream side
Upstream side
Upstream side
Downstream side
Marking line
Match mark
Marking line