INF-TN1FSH-E
- 67 -
4.4.9.5. Determining how to dispose of total at error (BURNOUT)
Description
Output burnout is a function of setting the total output to hold when measurement state becomes abnormal. Set the
duration until burnout processing is performed with the burnout timer.
(Setting contents)
•
Hold: Holds the total value
•
Not used: Burnout is not used.
Output burnout processing is performed as follows.
1. LCD .......................................Holds the total measurement value.
2. Total pulse output*
1
...............Stops output.
3. Internal
calculation*
1
.............Stops integration.
Note: Set output burnout in a state where total mode is set to total stop.
*1) Integration is continued until output burnout processing is started.
Operation
(example)
When setting output burnout to hold and burnout timer to 30 sec.
Key operation
Description
Display
FUNC TOTAL
Display “TOTAL MODE”
TOTAL MODE
TOTAL STOP
"
or
#
Select “OUTPUT BURNOUT”
OUTPUT BURNOUT
NOT USED
ENTER
"
or
#
ENTER
Enter select/enter mode, select “HOLD,”
and press ENTER.
OUTPUT BURNOUT
HOLD
#
Select “BURNOUT TIMER”
BURNOUT TIMER
10 sec
ENTER 3 0 ENTER
Enter numeric value enter mode, enter “30”
using ten keys, and press ENTER.
BURNOUT TIMER
30 sec
ESC
Return to “TOTAL MODE”
TOTAL MODE
TOTAL STOP
ENTER
"
or
#
ENTER
Enter select/enter mode, select “TOTAL
RESET,” and press ENTER.
TOTAL MODE
TOTAL RESET
ESC
Display the measurement, reflecting the
setting.
(Measurement display screen)