43
4.5
R
E
-
ZERO
P
RESSURE TRANSDUCERS
Ensure any external pressure transducers are connected to the Sentinel 2 at this stage.
•
Be sure to connect the inlet pressure transducer to the connector labelled “PRV
Inlet pressure”.
•
Be sure to connect the outlet pressure transducer to the connector labelled “PRV
outlet pressure”.
Ensure connectors are correctly fitted
so that they are watertight.
The transducers (internal or external)
must now be re-zeroed whilst in
atmospheric pressure
(not
connected to water pressure).
Select the Hardware Tests tab in IDT
and click the “Re
-
Zero” button.
Select the “PRV Inlet
pr
essure” transducer
by picking “Channel 1” on
the drop-down control.
Then click “OK”.