41
Choose the unit of measure next from the
list available in the
“Recording unit” selector.
Sentinel 2 and the PressView website both
require the Recording unit to be “
l
” for
correct operation.
Sentinel counts the meter pulses over a
logged period and converts them into a
“litres per second” measurement.
Sentinel
uses the units of litres / second as part of its
evaluation of whether to adjust the PRV
setting (if flow control is set).
The appropriate scaling factor
(Units per pulse) are also required.
e.g. If 1 pulse represents 10 litres,
“Units per pulse” should be set to “10”
.
“Logging Mode” should be set at “average” for
Sentinel 2; this will smooth-out any noise
(short fluctuations) in the readings and give a representative value of flow.
When com
pleted, click on “Accept” to update the configuration
being stored the IDT-PC
“current program” memory.
The channel settings are summarised in the
“Logging Channels” panel.
Note: Optional additional channels can be set in a similar manner to the 2 examples.
Decide if any statistical filtering will be applied to the incoming channel
data stream for creating datapoints in “logged data” memory.
•
Average (of a set of measurements)
•
Minimum (of a set of measurements)
•
Maximum (of a set of measurements)
•
Spot (a single measurement)