Figure 3. 50 y 50/51 IEEE Extremely Inverse
If overcurrent fault is 24xI
n
=12000 Ap, IEEE Extremely inverse curve defines a tripping value of 0.376 s
(Figure 3) for 50/51 function. It is considered that this time is too high, so when current fault reaches
24xI
n
, definite time overcurrent function will be work. 50 function tap is adjusted at 14xIn so definite time
overcurrent function will trip when current fault is higher than 14xIn (50 function does not wait to reach
24xIn)
The figure below (Figure 4), shows the tripping curve of the relay:
Figure 4. Relay tripping curve