4.9 Function 46BC. Broken conductor detection
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
46BC (*)
Broken conductor protection
Function Enable
-
-
No/Alarm/Trip
-
No
Current tap
15
100
1
%
50
Time Delay
0.020
300.000
0.001
s
0.200
(*) Optional depending on model
This protection detects the percentage phase unbalance due to an open phase condition. It considers
the measurement I2/I1 in percentage.
If the measured relation between I2 and I1 is higher (in percentage) than the setting in the function during
the adjusted time, the function will trip.
The function activates at 100% of the preset input and deactivates at 95%. The reset is instantaneous.
The accuracy of the time delay is equal to the set time delay ±30ms or ±0.5% (whichever is greater).
4.10 Function 49. Thermal Overload
This protection function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
49
Thermal overload
Function Enable
-
-
No/Alarm/Trip
-
No
Current Tap
0.100
2.400
0.001
xIn
1.200
ζ Heating constant
3
600
1
min
3
Cooling constant
1
6
1
ζ heating
1
Alarm
20
99
1
%
80
Thermal image is a measurement of heating and cooling of an electric machine. Contrary to an
overcurrent protection time is not counted when a fault is detected. It continues calculating the thermal
status of the monitored machine. Tripping time depends on adjusted thermal constants, operative
current and previous thermal status of the machine.
Thermal image is calculated based on next equation:
θ
= 100 x (I/It)
2
x (1
–
e-t/
ζ
) +
θ’0 x e
-t/
ζ
Summary of Contents for SIL-A A Series
Page 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Page 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Page 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Page 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Page 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Page 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Page 61: ...www fanox com Rev 04 61 112...
Page 63: ...www fanox com Rev 04 63 112...
Page 64: ...www fanox com Rev 04 64 112...
Page 65: ...www fanox com Rev 04 65 112...
Page 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...