There are 4 logic outputs “79N# Start” in the configurable logic. Default configuration is as follow:
Reclose Condition
Default Configuration
79N1 Start
General Trip AND 79 Standby
79N2 Start
General Trip AND 79 Reclose Nº 1
79N3 Start
General Trip AND 79 Reclose Nº 2
79N4 Start
General Trip AND 79 Reclose Nº 3
4.13.1 Counter to record the number of recloses
The SIL-A relay is fitted with a counter that records the number of recloses.
4.14 Function 50BF. Circuit Breaker failure
This control function can be set by using the following parameters:
Group
Description
Minimum
Maximum
Step
Unit
Default
50BF (*)
Circuit breaker failure
Function Enable
-
-
No/Yes
-
No
Time Delay
0.020
1.000
0.001
s
0.200
(*) Optional depending on model
The following automaton describes the open failure function:
Summary of Contents for SIL-A A Series
Page 8: ...www fanox com Rev 04 8 112 2 1 2 Case dimensions The dimensions are in mm...
Page 9: ...www fanox com Rev 04 9 112 2 1 3 Connection diagrams 2 1 3 1 Analog connections...
Page 12: ...www fanox com Rev 04 12 112 2 2 SILA with short circuitable current terminals 2 2 1 Front view...
Page 13: ...www fanox com Rev 04 13 112 2 2 2 Case dimensions The dimensions are in mm...
Page 14: ...www fanox com Rev 04 14 112 2 2 3 Connection diagrams 2 2 3 1 Analogic connections...
Page 22: ...www fanox com Rev 04 22 112 3 3 Functional diagram...
Page 61: ...www fanox com Rev 04 61 112...
Page 63: ...www fanox com Rev 04 63 112...
Page 64: ...www fanox com Rev 04 64 112...
Page 65: ...www fanox com Rev 04 65 112...
Page 111: ...www fanox com Rev 04 111 112 11 APPENDIX NOTES...