7.7.11. Settings
Menu
From the standby mode screen, press the “OK” key to access the first line of menus. Use
the “
▲
” and “
▼
” keys to position the cursor over the “SETTINGS” screen and press “OK”.
This takes you to the settings groups line. Use the “
▲
” and “
▼
” keys to position the cursor
over a settings group, and press the “OK” key to access the settings that belong to this
group. Use the “
▲
” and “
▼
” keys to move through the different settings. The information
that appears underneath the setting name is its value.
Press the “
◄
” key to access the general settings from the "SETTINGS" screen.
The general setting "Equipment name" can be viewed from the HMI, but it can only be
modified by using the SICom program.
The value of the "TI Phase ratio” and “TI Neutral ratio” general settings is the result given
by dividing the number of turns on the primary winding by the number on the secondary
winding. For example: With TI 500/5, the setting would be 100.
The frequency is selected for each model. The value is read only.
It is necessary to enter a password to change a setting for the first time. The settings can
be changed after entering the password, until returning either manually or automatically to
the standby mode screen. The system returns automatically to the standby mode screen if
no key is pressed for five minutes.
The factory setting password for the equipment is 5555. This password can be changed
using the SICom program.
The keys
▲
,
▼
,
◄
and
►
are used to enter the password.
▲
and
▼
are used to
introduce a value or a character, and the
◄
and
►
keys are used to move from one
character to another. If it is necessary to change one of the password characters or
numbers due to an error, press "
C
" to delete it. Press "
OK
” to validate the password.
Shown below is the sequence of steps to follow to change a setting:
Function Enable
NO
Set Password
>0
"OK" (password has not been set)
Set Password
>5555
Function Enable
NO -> NO
"OK"
Function Enable
NO -> YES
Function Enabled y/n?
NO -> YES
SETTING CHANGED
Function Enable
"OK"
Function Enable
YES
"OK"
"OK" (password is already set)
"OK"
Summary of Contents for SIA D
Page 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Page 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Page 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Page 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Page 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Page 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Page 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...