www.fanox.com
SIA-D_
Rev. 07
59 / 117
ISO 9001:2008
6.2. Standards
ELECTROMAGNETIC COMPATIBILITY TESTS
Nº
Test R
esul
t
STANDARD
APPLICATION IN:
A.C.
Power
Supply
D.C.
Power
Supply
Signal Ports
Metallic Box
Applied
COMMENTS
EMISSIONS
10
√
EN55022 (1998)
+A1 (2000)
+A2 (2003)
RF
Emissions
Class B
30-
230MHz:<30uV/m
230-
1000MHz:<37uV/m
√
IMMUNITY TO
20
√
IEC 61000-4-2
(1995)
+A1 (2000)
+A2 (2003)
Electrostatic
Discharges
Level 3
:
contact: ±6 kV
air: ±8 kV
√
21
√
IEC 61000-4-3
(2006)
ENV 50204
(1995)
Radiated
Radio-
frequency
Electro-
magnetic
Fields
Level 3
:
10 V/m AM
modulation; 80%
1KHz:
1) 80-1000MHz
2) 1000MHz-
2000MHz
√
Level 3
:
10 V/m PM
modulation; 50%
200Hz:
1) 900-1890MHz
√
22
√
IEC 61000-4-4
(2005)
Electrical
Fast
Transients
(EFT)
Level 4
:
±4 kV –
1) 15ms±20% at
5kHz
2) 0.75ms±20%
at 100kHz
Level 4
:
±2 kV
1) 15ms±20%
at 5kHz
2) 0.75ms±20%
at 100kHz
√
23
√
IEC 61000-4-5
(2007)
+A1 (2000)
Surges
Level 4
, Class 5
±2 kV Line-Line.
Coupling:2
Ω
/18
μ
F
±4 kV Line-
Ground.
Coupling:
12
Ω
/18
μ
F
Level 4
,Class 5
±2 kV Line-
Line.
Coupling:42
Ω
/0
.5
μ
F
±4 kV Line-
Ground.
Coupling:
42
Ω
/0.5
μ
F
√
Summary of Contents for SIA D
Page 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Page 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Page 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Page 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Page 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Page 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Page 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...