www.fanox.com
SIA-D_
Rev. 07
56 / 117
ISO 9001:2008
...Function
51N
Curve, activation level 120%
Curve, deactivation level 100%
Defined time, activation level 100%
Defined time, deactivation level 95%
Instantaneous deactivation
Timing accuracy: 5% or 30 ms (greater of both)
Trip blocking
Blocking level: 7 to 20 x In (step 0,01)
Function
67N
(2 units)
Permission: yes/no
Operating range I0: 0,10 to 30,00 x In (step 0,01)
Operating range V0: 4,00 to 110,00 V (step 0,1 V)
Operating time: 0,02 to 300 s (step 0,01 s)
Directionality: yes/no
Current, activation level 100%
Current, deactivation level 95%
Voltage, activation level 100%
Voltage, deactivation level 95%
Operating angle: 0 to 359º (step 1º)
Semicone angle: 0 to 170º (step 1º)
Circuit breaker monitoring
Circuit Brecker status: start, open, closed, error, opening time, opening error,
closing time, closing error
Input 52a and/or input 52b
Opening and closing command
Alarm, maximum number of openings: 1 a 10000
Alarm, accumulated amps: 0 a 10000 (kA²)
Excessive repeated openings: 1 a 10000
Time of excessive repeated openings: 1 a 300 min
Bus de disparo
Application: not activated, feeder, supply and feeder-supply
50P block permission: yes/no
51P block permission: yes/no
50N block permission: yes/no
51N block permission: yes/no
Summary of Contents for SIA D
Page 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Page 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Page 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Page 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Page 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Page 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Page 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...