9.14.3.
Reading the protection status of equipment nº 1
address
01
function
03
H start address
01
L start address
F5
Number of H registers
00
Number of L registers
3D
checksum H
95
checksum L
D5
And the SIA will reply with:
address
01
function
03
Number of Bytes
7A
50PStatus
00,09
51PStatus
00,00
50NStatus
00,00
51NStatus
00,00
GeneralStatus
00,00,00,D2
Inputs Status
80,21
Outputs Status
00,00
COM Status
00,03
RESERVED
checksum H
checksum L
00,00,00,01,00,00,00,00,……,7C,B1,0A,AF,DD 3B