4.10. Equipment settings
The SIA-D's settings are listed below with their description, maximums, minimums, units and the
values for the factory settings.
Group
Description
Minimum
Maximum
Step
Unit
Default
50P
Phases instantaneous overcurrent
Permission -
-
Yes/No
-
No
Tap 0,10
30,00
0,01
Inominal
5,00
Operating
time
0,02 300,0 0,01
s
0,02
51P
Phase inverse time overcurrent
Permission -
-
Yes/No
-
No
Curve - - (1*) -
Extremely
inverse
Dial 0,05
1,25
0,01 - 1,25
Tap 0,10
7,00
0,01
I
nominal
1,00
Operating
time
0,02 300,0 0,01
s
0,02
50N
Neutral instantaneous overcurrent
Permission -
-
Yes/No
-
No
Tap 0,20
30,00
0,01
I
nominal
1,00
Operating
time
0,02 300,0 0,01
s
0,02
51N
Neutral inverse time overcurrent
Permission -
-
Yes/No
-
No
Curve - - (1*) -
Extremely
inverse
Dial 0,05
1,25
0,01 - 1,25
Tap 0,10
7,00
0,01
I
nominal
0,50
Operating
time
0,02 300,0 0,01
s
0,02
Breaker blocking
Blocking - - Yes/No -
Yes
Blocking limit
7,00
20,00
0,01
I nominal
7,00
Summary of Contents for SIA D
Page 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Page 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Page 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Page 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Page 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Page 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Page 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...