The circuit breaker performance is shown in the following finite state machine:
The way that the circuit breaker is monitored becomes more or less complex depending on whether
it is fitted with one breaker contact (52a or 52b) or both (52a and 52b).
If only the circuit breaker 52a contact is available, it should be wired to the corresponding physical
input. This physical input is then assigned to the "52a Input” logical input. The 52b logical input is
calculated internally as the negative of 52a. The circuit breaker automata is considered as having
four statuses: start, open, closed and error.
If only the circuit breaker 52b contact is available, it should be wired to the corresponding physical
input. This physical input is then assigned to the "52b Input” logical input. The 52a logical input is
calculated internally as the negative of 52b. The circuit breaker automata is considered as having
four statuses: start, open, closed and error.
If both of the circuit breaker contacts 52a and 52b are available, they should be wired to the two
physical inputs. These physical inputs are then assigned to the corresponding logical inputs: the
circuit breaker 52a contact to the "52a Input" logical input, and the circuit breaker 52b contact to the
"52b Input" logical input. The circuit breaker's automata is considered as having eight statuses: start,
open, closed, error, opening time, opening fault, closing time and closing fault.
4.7.1. Circuit breaker opening and closing commands
The circuit breaker opening and closing commands are implemented. These commands can be
executed from the HMI command menu or through communications.
For the commands to have an effect, they should be assigned to the corresponding outputs. The
"Open circuit breaker" and "Close circuit breaker" bits are assigned to their corresponding outputs in
the "CONTROL" status group in the status menu.
Summary of Contents for SIA D
Page 1: ...www fanox com SIA D_Rev 07 1 117 ISO 9001 2008 USER MANUAL SIA D Overcurrent relay...
Page 36: ...www fanox com SIA D_Rev 07 36 117 ISO 9001 2008...
Page 37: ...www fanox com SIA D_Rev 07 37 117 ISO 9001 2008...
Page 38: ...www fanox com SIA D_Rev 07 38 117 ISO 9001 2008...
Page 58: ...www fanox com SIA D_Rev 07 58 117 ISO 9001 2008...
Page 60: ...www fanox com SIA D_Rev 07 60 117 ISO 9001 2008...
Page 116: ...www fanox com SIA D_Rev 07 116 117 ISO 9001 2008 10 8 NOTES...