3

DIP-SWITCH N° 3:

ON:

 Automatic closing

OFF:

 No automatic closing.

           Semi-automatic mode

T3

DWELL TIME

1 s - 180 s

-

+

FUNCTIONS

The acoustic device is inside the post and 
is on only during the rising and lowering 
movements of the post.

Beeper, post in motion:

Board power supply:

Description

Dip-switches and LED status of the various functions

7

DIP-SWITCH N° 7:

ON:

 Deadman control

OFF:

 Standard operating mode

Deadman control:

Open and Close operations are achieved “by holding a switch on” (no relay 
self-holding is involved). Therefore, a physical attendance is required during 
the entire cycle of movements until either the button or key is released.

Automatic / semiautomatic:

Automatic cycle:

 after a pulse to open, the bollard goes down, it stays stopped as long as the dwell 

time lasts, as pre-set by T3 trimmer, and on expiring of such time it goes up automatically.

Semi-Automatic cycle: 

after a pulse to open, the bollard goes down.

Another pulse is needed to close the gateway.

3

DIP-SWITCH N° 3:

ON:

 Automatic closing

OFF:

 No automatic closing.

           Semi-automatic operating mode

T3

DWELL TIME

1 s - 180 s

-

+

External time clock (optional):

CLOCK: the Elpro S50-T4 controller allows for a normal clock to be connected to it commanding the post 
to rise and lower.
Connections: parallel connect the NO contact of the clock to the terminals No. 4 open and No. 3 common, 
and set the controller to automatic mode by Dip-Switch n° 3 = ON.
How it works: set the clock to the required opening time. On the pre-set time the post is automatically 
lowered ( the indication light emits 2 short flashes followed by a longer pause). Any further 
command/pulsing (even by remote control) is not accepted by the system until the time pre-set on the 
clock is expired. On expiring of it, and after the pre-set dwell time, the post rises 
automatically.

DIP-SWITCHES N° 8 and N° 9:

Plug-in traffic lights card (optional):

The power supply of the traffic lights card is independent 
from that of the electronic control board:

230 V - 50 Hz

 with an output of 100 W at 230 V ea. lamp.

24 V

 with an output of 25 W each lamp.

12 V

 with an output of 22 W each lamp.

Functioning applies also to traffic lights with 2 lamps, red 
and green (Dip Switch 8 = OFF and 9 = OFF).

Functioning logic:

GREEN

 Light= post down, gateway 

OPEN

RED 

Light      = post moving or standing,

                                gateway 

CLOSED

YELLOW 

Light = it switches on before green turns

                                    to red light.

8

OFF

9

OFF

8

ON

9

OFF

8

9

OFF

ON

8

ON

9

ON

Dip-Switch 

8 = OFF

 and 

9 = OFF

Yellow turns on for 

0 s

 and after 

0 s

 

red turns on and 

the post starts 

rising immediately

Dip-Switch 

8 = ON

 and 

9 = OFF

Yellow turns on for 

2 s

, then red 

turns on and 

after 2 s the post 

starts rising

Dip-Switch 

8 = OFF

 and 

9 = ON

Yellow turns on for 

6 s

, then red 

turns on and 

after 5 s the post 

starts rising

Dip-Switch 

8 = ON

 and 

9 = ON

Yellow turns on for 

10 s,

 then red

turns on and 

after 7 s the post 

starts rising

RED

YELLOW

GREEN

Red

Yellow

Green

Fuse 1 A

(

Optional:

 plug-in traffic lights

card at a 230 V, 24 V or 12 V).
Item Code No. 

7282L

Red

Yellow

Green

Power supply

230 V - 50 Hz,

24 V or 12 V

Common

63 64 65 66 60 61

 BEEPER or 

LED

. C

OMMON

BEEPER

51 52 53

L1

N

L2 L3

L

N

L L

!

JUMPER

L-L-L

BOARD POWER

SUPPLY 400 V ± 10%

50 Hz THREE-PHASE

BOARD POWER

SUPPLY 230 V ± 10%

50 Hz SINGLE-PHASE

GB

CONTROLLER FOR TALOS M50

ANTI-TERRORISM RETRACTABLE BOLLARDS

Elpro S50-T4

Accessory

Electrical connections

Dip-switches and LED status of the various functions

11

Summary of Contents for Elpro S50-T4

Page 1: ...OMATIQUE OU SEMI AUTOMATIQUE PREPARE POUR HORLOGE EXTERNE FONCTION PAS PAS HOMME MORT F R AMPEL MIT 3 LICHTERN VORGESEHEN AUTOMATISCH ODER HALBAUTOMATISCH F R EXTERNE UHR VORGESEHEN SCHRITT F R SCHRIT...

Page 2: ...i ecc Eseguire una attenta analisi dei rischi utilizzando appositi strumenti di rilevazione di impatto e schiacciamento del bordo principale di apertura e chiusura secondo quanto indicato nella normat...

Page 3: ...L2 1 L1 6 T3 22 A2 4T2 2 T1 5 L3 21 L3 A1 3 L2 1 L1 25 84 25 84 21 20 19 19 73 75 74 73 finecorsa apertura TALOS 2 cavo grigio filo bianco finecorsa chiusura TALOS 2 cavo blu filo bianco finecorsa ap...

Page 4: ...nzioni 9 Gestione semaforo vedere riquadro delle funzioni 10 ON Lampeggiatore spento in pausa 11 ON Richiude in pausa dopo passaggio fotocellule 12 ON Tempo di lavoro massimo 90 s OFF 18 s Simbologia...

Page 5: ...W max di segnalazione del movimento Uscita 24 Vdc Motori Finecorsa T3 TEMPO DI PAUSA 1 s 180 s T1 TEMPO DI LAVORO 1 s 22 s 55 56 Led di segnalazione Uscita per led a luce intermittente sempre funzion...

Page 6: ...i nessun comando anche radio sino allo scadere del tempo impostato sull orologio allo scadere del quale dopo il tempo di pausa seguir la salita automatica DIP SWITCH N 8 e N 9 Schedina semaforo ad inn...

Page 7: ...pact force of the main opening and closing edge in compliance with EN 12445 Identify the appropriate solution necessary to eliminate and reduce such risks In case where the gate to automate is equippe...

Page 8: ...2 Contactor LOWERING M2 6 T3 22 A2 4T2 2 T1 5 L3 21 L3 A1 3 L2 1 L1 6 T3 22 A2 4T2 2 T1 5 L3 21 L3 A1 3 L2 1 L1 25 84 25 84 21 20 19 19 73 75 74 73 limit switch opening TALOS 2 grey cable white wire l...

Page 9: ...affic lights control see functions box 10 ON Flasher off in dwell time 11 ON Close in dwell time after passing between photocells 12 ON Motor run time max 90 s OFF 18 s Symbols NO Contact NC Contact L...

Page 10: ...lways on blinking during the rising and lowering movements of the post and with the post in standing position They go off with post in down position 200 mA for the accessories LEDs or BEEPER COMMON LE...

Page 11: ...further command pulsing even by remote control is not accepted by the system until the time pre set on the clock is expired On expiring of it and after the pre set dwell time the post rises automatic...

Page 12: ...en utilisant instruments de d tection de l impact et crasement du bord principale d ouverture et fermeture conform ment aux normes EN 12445 D finir les solutions appropri es pour liminer ou r duire t...

Page 13: ...e course ouverture TALOS 1 c ble gris fil blanc fin de course fermeture TALOS 1 c ble bleu fil blanc 73 74 75 F 20 A MOTEUR 2 borne escamotable 230 V monophas 19 20 21 COMMUN M2 F 20 A 76 77 78 MOTEUR...

Page 14: ...stion du feu de circulation voir le tableau des fonctions 9 Gestion du feu de circulation voir le tableau des fonctions 10 ON Lampe clignotante teinte en pause 11 ON Referme en pause apr s le passage...

Page 15: ...endant le mouvement de mont e et de descente et en arr t avec la borne en position lev e Elles s teintent avec la colonne baiss e COMMUN LED ET OU BEEPER LED 51 52 53 MOTEUR 1 Borne escamotable 1 16 1...

Page 16: ...s longue Il n acceptera plus aucune commande m me radio jusqu l xpiration du temps tabli sur l horloge A l xpiration de ce temps apr s le temps de pause il y aura la mont e automatique DIP SWITCH N 8...

Page 17: ...etc F hren Sie eine sorgf ltige Risikoanalyse unter Verwendung geeigneter Instrumenten zur Erkennung von Schlag und Druck der Vorderkante des ffnen und Schlie en wie in EN 12445 festgelegt Identifizi...

Page 18: ...1 14 15 26 14 15 26 Contactor RISING M2 Contactor LOWERING M2 6 T3 22 A2 4T2 2 T1 5 L3 21 L3 A1 3 L2 1 L1 6 T3 22 A2 4T2 2 T1 5 L3 21 L3 A1 3 L2 1 L1 25 84 25 84 21 20 19 19 73 75 74 73 ffnung Endscha...

Page 19: ...ionen 9 Ampel Steuerung Sehen Sie Abschnitt Funktionen 10 ON Blinkleuchte Off in Pause 11 ON Es schlie t wieder in Pause nach Durchgang durch Lichtschranke 12 ON Max Betriebszeit 90 s OFF 18 s Symbole...

Page 20: ...LOS 4 graunes Kabel wei er Draht Schlie ung Endschalter TALOS 4 blaues Kabel wei er Draht POLLER 1 MOTOR 1 16 17 18 M1 COMMON POLLER 2 MOTOR 2 19 20 21 COMMON M2 POLLER 3 MOTOR 3 31 32 33 COMMON M3 PO...

Page 21: ...ies mit zweimaligem kurzen Blinken gefolgt von einer l ngeren Pause Bis nach Ablauf der auf der Uhr eingestellten Zeit wird es kein andere Befehl mehr angenommen auch nicht ber die Fernbedienung nachd...

Page 22: ...Elpro S50 T4 22...

Page 23: ...20 C 55 C Solenoid valve power supply 230 Vac 50 Hz Beeper output 230 Vac 100 W GB CARACTERISTIQUES TECHNIQUES Alimentation carte monophas e 230 Vac 10 50 Hz Alimentation carte triphas e 400 Vac 10 50...

Page 24: ...www fadini net IT Direttiva 2012 19 UE Smaltimento dei materiali elettrici ed elettronici VIETATO GETTARE NEI RIFIUTI MATERIALI NOCIVI PER L AMBIENTE GB Directive 2012 19 UE Disposal of electric and e...

Reviews: