code
7282L
FUNCTIONS
M1
M2
11
S20
meccanica
FADINI
GB
ELECTRONIC PROGRAMMER UP TO 2 BOLLARDSWITH OR WITHOUT LIMIT SWITCHES
3
DIP-SWITCH 3
Automatic / Semi-automatic:
T2
-
+
Automatic cycle
: after an opening pulse, the bollard goes down, it stops for dwell time pre-set in trimmer
T2, after the pre-set time it closes automatically
Semi-Automatic
: after an opening pulse, the bollard goes down.
A closing pulse is needed to close.
Dwell time
from 1 to 180s
ON= Automatic closing
OFF= No automatic closing.
Semi-automatic function
Dwell time
from 1 to 180s
T2
-
+
Input P
57 58
6
DIP-SWITCH 3 - 6 both on ON
3
ON= Automatic closing
OFF= No automatic closing
semi-automatic closing
Pedestrian Opening:
This command is separate from the standard
opening command. When all the posts are in up
position, on pulsing input P Dip-Switch 6= On,
and 3=On , post n
1 (Motor M1) goes down for
pedestrian opening, for the time pre-set in
Trimmer T2, after this time it closes automatically.
The function "Pedestrian Opening" is not in service
during the first operation cycle, after a power failure.
Pedestrian opening
contact terminals
Post Motor M1
ON= Pedestrian opening Motor M1
OFF= Standard operation
DIP-SWITCH 7
7
Hold on switched (Deadman) control:
Open and Close operations are achieved “by holding a switch on”
(no relay self-holding is involved) therefore a physical attendance is
required to keep the post opening or closing until either the button
or key is released.
ON= Deadman control
OFF= Standard operations
External Clock (Optional):
DIP-SWITCH N
3=ON Automatic closing
3
Dwell time
from 1 to 180s
T2
-
+
4
3
COMMON
OPEN
NO
External clock
CLOCK: The electronic programmer Elpro S20 can be connected to a clock for the post opening and closing.
Connection: connect in parallel the NO clock contact to the 4 OPEN and 3 COMMON terminals, automatic closing is by
Dip-Switch n
3=ON
How it works: Set the clock to the required time. On the pre-set time the post is automatically opened (the post goes
down) and held open (the flashing light goes off and the led flahes twice and dwells). Any further pulsing (even by remote
control) is not accepted by the system until the time pre-set by the clock has expired. On expiring and after the pre-set
dwell time the post rises automatically.
COMMON
ON= Automatic closing
OFF= No automatic closing.
Semi-automatic function
DIP-SWITCHES 8 and 9
8
OFF
9
OFF
8
ON
9
OFF
8
9
OFF
ON
8
ON
9
ON
63 64 65 66
60 61
Plug-in traffic lights interface (Optional):
The interface power supply (230V 50Hz 100W output per lamp) is independent from the one of the programmer.
It can work also with the 2 lamps, Red and Green traffic lights (Dip Switch 8=OFF and 9=OFF)
Working logic
:
-
GREEN
Light= Post in
down position
,
OPEN
passage
-
RED
Light=
Moving post or in
up position
,
CLOSED
passage
-
YELLOW
Light= it lights before the switching from the Green light to the Red light
Note
: During
Pedestrian mode
the traffic light is always
RED
.
Dip-Switch
8=OFF
and
9=OFF
The yellow light turns on for the time of
0s
and after
0s
the Red
light turns on
and the post starts rising immediately
Dip-Switch
8=ON
and
9=OFF
The yellow light turns on for the time of
2s
then the Red light
turns on and
after 2s the post starts rising
Dip-Switch
8=OFF
and
9=ON
The yellow light turns on for the time of
6s
then the Red light turns
on and
after 5s the post starts rising
Dip-Switch
8=ON
and
9=ON
The yellow light turns on for the time of
10s
then the Red
light turns on and
after 7s the post starts rising
RED
YELLOW
GREEN
Red
Y
ellow
Green
Common
Power supply
230V 50Hz
Fuse 1A
Red
Yellow
Green
(
Optional:
Plug-in PCB for
230V traffic lights)