These instructions apply to the following models:
MASTER-T AND SLAVE-T CONTROL BOARDS FOR DOMO SWING AUTOMATED SYSTEMS
The DOMO automated system consists of non-reversing electro-mechanical operators, powered by 12 Vdc, through toroidal
transformer and power supply board; each coupled to a control board.
The SLAVE-T control board (required on 2-leaf gates only) is controlled by the MASTER-T control board to which all accessories and
pulse generators are connected. The MASTER-T board can be programmed and is used to set the following: function logics, work
times (by self-learning) and pause times, leaf speed, and the sensitivity of the anti-crushing device.
The DOMO automated system was designed and built for controlling vehicle access. Do not use for any other purpose.
DOMO MASTER-T - SLAVE-T CONTROL BOARD
1.
DESCRIPTION
Fig. 1
a
Control board
b
Board support
c
Power unit board
d
Toroidal transformer
e
Terminal board (MASTER-T only)
f
Enclosure in class IP 55
햳
햴
햲
햵
햷
햶
2.
DIMENSIONS
Fig. 2
•
Dimensions in mm
CONTROL BOARD
ENCLOSURE
5.
MASTER-T AND SLAVE-T BOARDS COMMON
TECHNICAL SPECIFICATIONS
Power supply Vac
230 (+6% -10%) ~ 50/60Hz
Use frequency (cycles/hour)
15
(1)
Consecutive cycles
30
(1)
Recovery time
2' for each completed cycle
(1)
Enclosure protection class
IP 55
Transformer power
180 VA
Motor max current
15A
Operating ambient temperature
-20°C ÷ +55°C
Protection fuses
1 fuse 20A
Anti-crushing function
Encoder - Current control
4. SLAVE-T BOARD TECHNICAL SPECIFICATIONS
Terminal board outputs
Motor
Terminal board inputs
Power Supply Unit - Bus
3. MASTER-T BOARD TECHNICAL SPECIFICATIONS
Accessories max. load at 24 Vdc
150 mA
Rapid connector max load
50 mA
Function logics
Automatic / “Stepped” automatic / Safety
device/ “Stepped” semi-automatic
Opening/closing time
By self-learning
Pause time
Programmable: 5, 10, 20, 30 sec.
Opening and closing leaf delay time
(op 0s, cl 0s) - (op 2s, cl 2s) - (op 2s, cl 4s) - (op 2s, cl 8s)
Speed
Selectable on 4 levels
Static force adjustment
Selectable on 4 levels
Terminal board inputs
Power Supply Unit -
Open - Free leaf open - Stop - Op. safety devices - Cl. safety
devices
Terminal board outputs
Flashing lamp - Motor - Bus -
indicator-light - Accessories 24 Vdc - 12 Vdc power supply
Rapid connector
Decoder / minidec / RP cards
Programmable functions
Logic - pause time - leaf opening
and closing delay - anti-crushing force - operators speed
(1)
The 15 cycles/hour are just a reference value for maintaining full
efficiency of motorisation. 30 consecutive cycles can be performed
with software thermal protection. Recovery time is 2' each cycle
performed.