background image

2.1

INSTRUCTIONS FOR USING BATTERIES

The batteries last for about twenty hours of continuous
operation.
For correct use of the batteries observe the following
instructions:
-Do not use old and new batteries or different types of
batteries at the same time.
-The batteries must be changed when the FAACTOTUM
display indicates that the charge is running out.
-The batteries must not be exposed to excessive heat or to
naked flames and they must be handled with care.
-If the FAACTOTUM remains inactive for long periods of time,
it is advisable to take the batteries out and to keep them in
a suitable place.
-If acid leaks from the batteries, remove them and clean
the inside of the compartment thoroughly before inserting
new ones.
-Do not use rechargeable batteries.
-Do not attempt to recharge alkaline batteries.
-Dispose of used batteries by placing them in the special
containers for differentiated waste collection.

3.

CONNECTION TO AN EXTERNAL POWER PACK

The FAACTOTUM (Fig. 3) has a socket for connection to an
external power pack (not provided).

The external power pack connector is suitable for the use of most
commercially available power packs.
It is however important to check that the power pack
characteristics and the plug polarity meet the requirements
of table 1.
The external power pack allows the FAACTOTUM to be used
when it is not connected to the electronic control unit 460P.
The FAACTOTUM can be connected to the power pack with the
batteries fitted since the external power source is used
preferentially to save battery charge.
The internal batteries operate as a buffer supply,  cutting in if
the power pack fails.
Do not use the power pack when the FAACTOTUM is connected
to the electronic control unit.

This connection is required whenever it is necessary to transfer
a program onto the card, to change the program already
present or to perform diagnostics and check the functionality
of the automation.
Fit one of the two male connectors (it doesn’t matter which)
located at the end of the cable onto the FAACTOTUM
connector (Fig. 4) and the other onto the connector on the
460P card or on the expansion modules, if any are installed
(Fig. 5).
The connectors are specially-shaped to ensure that they are
inserted the right way round.
When the FAACTOTUM is connected to the card and the
card is powered, it is the card that supplies the programmer
with the electrical current required for operation.
In this case, if the batteries are present the power supply
from the card is used preferentially to save battery charge.

4.

CONNECTION TO  460P

The connection between the FAACTOTUM and the 460P card
is made using the 20-wire flat cable provided.

Fig. 4

Fig. 5

Fig. 3

Warning: when disconnecting the cable from the control
unit or the FAACTOTUM, do not pull the cable directly but
instead hold onto the connector.

2

Table 1     External power pack characteristics
output voltage

12 Vdc

c u r r e n t

100 mA

connector type

for dc Ø 2.1 mm

connector polarity

positive inside

Summary of Contents for FAACTOTUM

Page 1: ...FAACTOTUM FAACTOTUM R...

Page 2: ......

Page 3: ...ms or it can be modified Besides programming the FAACTOTUM can be used to perform diagnostics and to check the operation of the automation and the connection to an external PC appropriate software pro...

Page 4: ...rol unit 460P The FAACTOTUMcanbeconnectedtothepowerpackwiththe batteries fitted since the external power source is used preferentiallytosavebatterycharge The internal batteries operate as a buffer sup...

Page 5: ...LP When enabled this key provides useful information regarding programming 8 SHIFT SHIFT Press this key to activate the alternative function of keys which have a double function e g alphanumeric keys...

Page 6: ...his function prevents the FAACTOTUM from being used by anyone who does not know the password but it does not prevent access to the configuration saved on the 460P card Select the mode by moving the ar...

Page 7: ...cter alphanumeric identification If you know the number enter it the corresponding identification will appear and press ENTER Alternatively pressing the and keys displays all the memory locations one...

Page 8: ...uses a short closure movement before the leaves open to facilitateoperationoftheclosedpositionelectriclocks Selectoption 1 Inversion stroke enabled 2 Inversion stroke disabled 1 F1 2 F2 or ENTER Make...

Page 9: ...through the logics avail able and their identifications When the desired logic appears press ENTER to select it If you know the location key in the number the identification appears and press ENTER o...

Page 10: ...rrow on the display moves to select the effect of the subsequent pulse Close Leaf 2 completely and press ENTER cont ASSOCIATE CHOSEN FUNCTION WITH INPUT AND PRESS ENTER INP 2 XXXXXX ENTER INPUT MODULE...

Page 11: ...eviously been set When the key is pressed Leaf 2 begins to close and the arrow on the display moves alongside the DECELERATION option When Leaf 2 has reached the position where you wish closing decele...

Page 12: ...s for entering the register value DEC to enter the register value in decimal BIN to enter the register value in binary If DEC is selected enter the value using the number keys If BIN is selected press...

Page 13: ...After entering the identification press ENTER to save and proceed If you select an occupied location saving will cause the resident configuration to be overwritten A K U C M W E O Y G Q I S B D F H J...

Page 14: ...omplete diagnostics on the automation the FAACTOTUM must be connected to the 460P electronic control unit Press ENTER to continue ENTER The menus contained in the diagnostics with the exception of the...

Page 15: ...IMPULSE COMMAND 1 OPEN A 2 OPEN B 3 STOP 4 CLOSE ESC TO EXIT From the time of its installation the 460P counts the number of cycles performed by the automation to give an idea of its degree of usage...

Page 16: ...nfiguration on the card it can be loaded from this menu Select option 1 Load 460P standard configuration resident in the FAACTOTUM 2 Ignore the question and proceed 1 F1 2 F2 SELECT MODE 14 1 F1 2 F2...

Page 17: ...time as the Gatecoder and vice versa 5 With the sole exception given below it is not possible to assign the same function to more than one terminal 6 The 460P card terminal IN2 can also be configured...

Page 18: ...XXXXXX 60Hzmainspowersupply 30 XXXXXXX0 FAILSAFEoninputFSW CLdisabled disabled XXXXXXX1 FAILSAFEoninputFSW CLenabled XXXXXX0X FAILSAFEoninputFSW OPdisabled disabled XXXXXX1X FAILSAFEoninputFSW OPenabl...

Page 19: ...mand The contact remains closed until the state is reset REG No VALUE FUNCTION DEFAULT 14 1001XXXX panicstateactivated 0000XXXX Default standardwarninglightfunction 3 Automation open state contact The...

Page 20: ...ds 14 11 ELECTRIC LOCK ACTIVATION TIME Sets the duration of electric lock activation Thesetvaluemustbelowerthantheopeningandclosingleaf delay times REG No VALUE FUNCTION DEFAULT 56 seconds electric lo...

Page 21: ......

Page 22: ......

Reviews: