The states of all inputs on the 460P card terminal block (inputs 1-5) and on the MEI
module if present (inputs 6-11) are displayed in real time.
By activating the activation device connected to each input it is possible to
verify operation by noting the change in status of the symbol alongside:

=  Contact open

=  Contact closed

N.B.:
1)  The inputs are numbered according to the physical layout of the terminal
block without taking account of the meaning assigned to them. The correctness
of the state of the input must be determined according to the function assigned
to the terminal.
2)  When the Gatecoder is used, the respective input shows a sequence of con-
tact open/closed states when the gate is moving.
Press ENTER to proceed.

ENTER

9.

DIAGNOSTICS

ENTER

CONNECT TO 460P

AND PRESS ENTER

CHECK VOLTAGES

Vbat +Vrl +5V Vacc

^

^

^

^

OK

OK

OK

OK

ENTER

12

The FAACTOTUM checks the following voltages:
Vbat   = FAACTOTUM internal battery voltage
Vrl      = 460P card relay power supply voltage (12Vdc)
+5V    = 460P card logic power supply voltage (5Vdc)
Vacc  = Accessories power supply voltage (24Vdc)
The message OK appears next to each correct voltage.
If this message does not appear for one or more voltages, this means that the
measured voltage is lower than it should be or is absent.
For further information, read chapter 11 “Checking voltages”.

ENTER

To perform complete diagnostics on the automation, the FAACTOTUM must be
connected to the 460P electronic control unit.
Press ENTER to continue.

ENTER

The menus contained in the diagnostics (with the exception of the voltage check menu) are shown
only if the FAACTOTUM is connected to the card.
These menus provide valuable assistance for checking the functionality of the system and for diagnostics,
and also provide information on the degree of usage of the automation.

SOFTWARE VERSION

460P

X.X

The 460P card software version is shown.
Press ENTER to continue.

ENTER

During installation, before performing the time learning cycle, it is advisable to check that the
automation is working correctly by performing the motor check.
The by-pass valves should also be regulated by following the specific instructions for the hydraulic
operator.

INPUT STATES

 1    2     3     4     5
 6     7     8     9     10    11

ENTER

The following information is displayed in real time:

1) STATE

= State of the automation

The envisaged states are:
-CLOSED

= Gate closed

-PREFL.OPEN

= Opening pre-flashing

-OPENING

= Gate opening

-OPEN TMP

= Timed opening (operation of closure safety edge)

-OPEN

= Gate open

-PAUSE

= Gate on pause

-PREFL.CLOS

= Closure pre-flashing

-CLOSING

= Gate closing

-CLOS.TMP

= Timed closure (operation of opening safety edge)

-STOP OPEN

= Stops then opens

-STOP CLOS.

= Stops then closes

-STOP FSW-C

= Closure safety tripped

-STOP FSW-O

= Opening safety tripped

-PANIC

= Panic opening device control activated

-PROGRAMM.

= Programming

ENTER

    GATE STATE

STATE

CLOSED

LAMP

OFF

OUT F.TX

ON

RX OK

ENTER

ENTER

(cont.)

(cont.)

Summary of Contents for FAACTOTUM

Page 1: ...FAACTOTUM FAACTOTUM R...

Page 2: ......

Page 3: ...ms or it can be modified Besides programming the FAACTOTUM can be used to perform diagnostics and to check the operation of the automation and the connection to an external PC appropriate software pro...

Page 4: ...rol unit 460P The FAACTOTUMcanbeconnectedtothepowerpackwiththe batteries fitted since the external power source is used preferentiallytosavebatterycharge The internal batteries operate as a buffer sup...

Page 5: ...LP When enabled this key provides useful information regarding programming 8 SHIFT SHIFT Press this key to activate the alternative function of keys which have a double function e g alphanumeric keys...

Page 6: ...his function prevents the FAACTOTUM from being used by anyone who does not know the password but it does not prevent access to the configuration saved on the 460P card Select the mode by moving the ar...

Page 7: ...cter alphanumeric identification If you know the number enter it the corresponding identification will appear and press ENTER Alternatively pressing the and keys displays all the memory locations one...

Page 8: ...uses a short closure movement before the leaves open to facilitateoperationoftheclosedpositionelectriclocks Selectoption 1 Inversion stroke enabled 2 Inversion stroke disabled 1 F1 2 F2 or ENTER Make...

Page 9: ...through the logics avail able and their identifications When the desired logic appears press ENTER to select it If you know the location key in the number the identification appears and press ENTER o...

Page 10: ...rrow on the display moves to select the effect of the subsequent pulse Close Leaf 2 completely and press ENTER cont ASSOCIATE CHOSEN FUNCTION WITH INPUT AND PRESS ENTER INP 2 XXXXXX ENTER INPUT MODULE...

Page 11: ...eviously been set When the key is pressed Leaf 2 begins to close and the arrow on the display moves alongside the DECELERATION option When Leaf 2 has reached the position where you wish closing decele...

Page 12: ...s for entering the register value DEC to enter the register value in decimal BIN to enter the register value in binary If DEC is selected enter the value using the number keys If BIN is selected press...

Page 13: ...After entering the identification press ENTER to save and proceed If you select an occupied location saving will cause the resident configuration to be overwritten A K U C M W E O Y G Q I S B D F H J...

Page 14: ...omplete diagnostics on the automation the FAACTOTUM must be connected to the 460P electronic control unit Press ENTER to continue ENTER The menus contained in the diagnostics with the exception of the...

Page 15: ...IMPULSE COMMAND 1 OPEN A 2 OPEN B 3 STOP 4 CLOSE ESC TO EXIT From the time of its installation the 460P counts the number of cycles performed by the automation to give an idea of its degree of usage...

Page 16: ...nfiguration on the card it can be loaded from this menu Select option 1 Load 460P standard configuration resident in the FAACTOTUM 2 Ignore the question and proceed 1 F1 2 F2 SELECT MODE 14 1 F1 2 F2...

Page 17: ...time as the Gatecoder and vice versa 5 With the sole exception given below it is not possible to assign the same function to more than one terminal 6 The 460P card terminal IN2 can also be configured...

Page 18: ...XXXXXX 60Hzmainspowersupply 30 XXXXXXX0 FAILSAFEoninputFSW CLdisabled disabled XXXXXXX1 FAILSAFEoninputFSW CLenabled XXXXXX0X FAILSAFEoninputFSW OPdisabled disabled XXXXXX1X FAILSAFEoninputFSW OPenabl...

Page 19: ...mand The contact remains closed until the state is reset REG No VALUE FUNCTION DEFAULT 14 1001XXXX panicstateactivated 0000XXXX Default standardwarninglightfunction 3 Automation open state contact The...

Page 20: ...ds 14 11 ELECTRIC LOCK ACTIVATION TIME Sets the duration of electric lock activation Thesetvaluemustbelowerthantheopeningandclosingleaf delay times REG No VALUE FUNCTION DEFAULT 56 seconds electric lo...

Page 21: ......

Page 22: ......

Reviews: