background image

Istruzioni ed avvertenze per l’installazione e l’uso

Instructions and warnings for installation and use

Instrucciones y advertencias para su instalación y uso

Anleitungen und Hinweise zu Installation und Einsatz

Instruções e advertências para a instalação e utilização

Instructions et avertissements pour l’installation et l’usage

Management

System

ISO 9001:2008

www.tuv.com

ID 9105043769

Kit di alimentazione con pannello fotovoltaico per l’automazione di cancelli e barriere

Solar power kit for the automation of gates and barrier gates

SOLE

Summary of Contents for PF30W

Page 1: ...und Hinweise zu Installation und Einsatz Instruções e advertências para a instalação e utilização Instructions et avertissements pour l installation et l usage Management System ISO 9001 2008 www tuv com ID 9105043769 Kit di alimentazione con pannello fotovoltaico per l automazione di cancelli e barriere Solar power kit for the automation of gates and barrier gates SOLE ...

Page 2: ...el prodotto Staffa di montaggio del pannello solare Pannello solare Regolatore di carica solare Pressacavi e cavi Cablaggio Istruzioni per l uso Simboli Indicazioni a display Impostazione tipo di batteria Impostazione numero seriale Impostazioni di ricarica Modalità di funzionamento Risoluzione dei problemi Codice di errore e correzione Sintomi e correzione pag 3 pag 4 pag 4 pag 4 pag 4 pag 5 pag ...

Page 3: ...cavo di alimentazione risulta danneggiato esso deve essere sostituito dal costruttore o dal suo servizio di assistenza tecnica o comunque da una persona con qualifica similare in modo da preve nire ogni rischio se sostanze liquide penetrano all interno delle parti dei componenti dell automazione scollegare immediatamente l alimentazione elet trica e rivolgersi al Servizio Assistenza Key Automation...

Page 4: ...o dall utente 27 6V 28 8V 2h 29 2V 2h 28 giorni Consigliamo di usare 2 batterie 12V 18Ah tipo AGM SCHEDA CONTROLLO INPUT VALORE Tensione ingresso MAX PV 50V Corrente nominale 20A OUTPUT VALORE Tensione uscita impianto 24V HVD Tensione massima disconnessione 32V Corrente di scarica nominale 20A Autoconsumo 13mA Caduta di tensione del circuito di carica 0 21V Caduta di tensione circuito di scarica 0...

Page 5: ...rraggiamento e temperatura delle celle 1000W m AM1 5 25 C Picco di potenza Pmax 30W Tensione a Pmax Vmp 34 4V Corrente a Pmax Imp 0 87A Tensione a circuito aperto Voc 43 2V Corrente di cortocircuito Isc 0 96A Temperatura di esercizio 40 85 C Dimensioni 510 x 541 x 30 mm Peso 3 75 k g Anche se il nostro sistema può funzionare per oltre 30 cicli e o fornire oltre 1 settimana di funzionamento in stan...

Page 6: ...GY SAVING 1 0 0235 0 56 MA24 con due PO24 cancello chiuso in stand by senza accessori ENERGY SAVING 1 0 0210 0 51 in stand by senza accessori con RX4X RX4Y ENERGY SAVING 1 0 0250 0 6 FT32 22 un TX e un RX durante l attivazione in function 0 0290 0 69 ECLIPSE Luce di CORTESIA accesa in function 0 0325 0 77 Lampeggiante acceso in function 0 0200 0 99 LED strip 18 led in function 0 0325 0 77 For MA24...

Page 7: ...in SBY can cello aperto Ore cancello chiuso Ore cancello aperto corrente totale A cancello chiuso posizione A corrente totate A cancello aperto posizione B MA24 PO24 RX4Y 0 0235 0 0235 22 8 0 4 0 535 0 009 FT32 0 0 0290 0 0 4 0 0 011 ECLIPSE lampeggiante 0 0 22 8 0 0 0 striscia LED ECLIPSE 0 0 22 8 0 0 0 Striscia LED cover SUN 0 0 22 8 0 0 0 TOTAL 0 535 0 02 Consumo giornaliero in standby Prodotto...

Page 8: ...ga quindi fermo se lasciato in qualsiasi posizione verificare che tutto il materiale utilizzato per l installazione sia confor me alle normative vigenti Contattare il personale tecnico per smantellare o riparare il prodotto Tenere il luogo di installazione lontano da gas infiammabili esplosivi sostanze corrosive polvere ecc Evitare che oggetti estranei o liquidi si avvicinino alla centrale Non met...

Page 9: ...i fori per il montaggio se si utilizza questo supporto con un pannello diverso dal PF30W Prestare molta attenzione quando si praticano fori aggiuntivi in quanto si possono facilmente danneggiare i pannelli renden doli inutilizzabili ATTENZIONE α fig 4 che deve essere calcolato sulla base della seguente tabella Latitudine Angolo di inclinazione α 0 15 15 15 25 stesso valore della latitudine 25 30 A...

Page 10: ...premuto un tasto qualsiasi se si verifica un errore dopo 20 secondi di assenza di operazioni viene presentata l interfaccia del codice di errore Per attivre o disattivare la carica nell interfaccia Tensione batteria o Codice errore premendo brevemente Nell interfaccia 5 2 Indicazioni a dislay 5 3 Impostazione tipo di batteria Impostare la tensione del sistema su 24V Ah Battery Charge Meter o Ah Ba...

Page 11: ...quattro tipi di batteria GEL SLD FLD e USr Solo i parametri del tipo USr sono regolabili 5 4 Impostazione numero seriale regolatore di carica 5 5 Impostazioni di ricarica livello di tensione una pressione prolungata 3s o un assenza di operazioni per 20 secondi di funzionamento Comunicazione controller SN composta da 8 cifre ogni 2 cifre visualizzate in sequenza ad es 88 56 73 24 possibile modifica...

Page 12: ...re la quantità del pannello solare in connessione parallela e attendere 2 minuti per la ricarica di riavvio Sintomi Controlli LCD non is attiva Verificare il collegamento delle batterie assicurarsi che il fusibile sia intero e correttamente collegato No charging current Verificare la polarità che i cavi siano correttamente coillegati e in buone condizioni Carico non funzionante Accertarsi che il c...

Page 13: ...talling the product Solar panel mount bracket Solar panel Solar charge controller Cable and cable glands Wiring Operating Instruction Symbols LCD Interfaces Battery communication Controller SN Charging settings Load working mode Troubleshooting Error code and correction Symptoms and correction pag 14 pag 15 pag 15 pag 15 pag 15 pag 16 pag 16 pag 16 pag 17 pag 19 pag 24 pag 20 pag 20 pag 20 pag 20 ...

Page 14: ...fications to prevent all risks do not allow parts of the automation system to be immersed in water or other liquids During installation ensure that no liquids are able to enter the various devices should this occur disconnect the power supply immediately and contact a Key Automation Service Centre Use of the automation system in these conditions may cause hazards never place automation system comp...

Page 15: ...7 6V 28 8V 2h 29 2V 2h 28 day We strongly suggest to use 2 GEL batteries 12V 18Ah AGM absorbent glass mat type SOLAR CHARGE CONTROLLER INPUT VALUE PV voltage 50V Rated current 20A OUTPUT VALUE System voltage 24V HVD 32V Rated discharge current 20A No load loss 13mA Charge loop voltage drop 0 21V Discharge loop voltage drop 0 12V Charging mode PWM Multi stage bulk absorption float equalized Voltage...

Page 16: ...essories you connect the more power your system will require The SOLE KIT solar powered system is intended for resi dential applications and light commercial gate operation with limited cycles per day SOLAR PANEL PARAMETERS VALUE Model SLP030W 24V Cells polycrystalline silicon solar cell Irradiance and Cell Temperature 1000W m AM1 5 25 C Peak Power Pmax 30W Voltage at Pmax Vmp 34 4V Current at Pma...

Page 17: ... during activation in function 0 0290 0 69 ECLIPSE COURTESY light on in function 0 0325 0 77 FLASHLIGHT on in function 0 0200 0 99 LED strip 18 leds in function 0 0325 0 77 For MA24 no DYL display connected Example of installation with SUN11024 and with 12 hours Night Light System NLS Eclipse cover LED strip and without Night Light System ATTENTION DATA VALUE DESCRIPTION Location Venice Italy Slid...

Page 18: ...gate closed consumption A h in SBY gate open hours closed hours gate open total A gate position closed A total A gate position open B MA24 PO24 RX4Y 0 0235 0 0235 22 8 0 4 0 535 0 009 FT32 0 0 0290 0 0 4 0 0 011 ECLIPSE flashlight 0 0 22 8 0 0 0 ECLIPSE LED strip 0 0 22 8 0 0 0 LED strip cover SUN 0 0 22 8 0 0 0 TOTAL 0 535 0 02 Standby consumption day Product Consumption work cycle A Hours day To...

Page 19: ...ilibrium and stationary if left in any position Ensure that all materials used for the installation comply with current regulations Contact technical personnel to dismantle or repair the controller Keep installation site clear of flammable or explosive or corrosive gases and dust etc Prevent foreign object or liquid approaching controller Don t put metal object beside battery Do not touch terminal...

Page 20: ... wall surface 4 1 Solar panel mount bracket Additional mounting holes may be required if using this mount with a panel other than the PF30W Great care should be taken when drilling additional holes as damage to the panel can easily occur rending it useless ATTENTION lated based on the following table Latitude Tilt angle α 0 15 15 15 25 same value as the latitude 25 30 Add 5 to the latitude value 3...

Page 21: ...play presents the current interface until press any key if there s failure after 20s absence of key operation the error code interface is presented In interface Battery voltage or Error code by short pressing load is switched on or off 5 2 LCD Interfaces 5 3 Battery communication Set System voltage to 24V In interface Ah Battery Charge Meter or Ah Battery Discharge Meter by long pressing 3S data i...

Page 22: ...d a 20s absence of operation bring you to main loop interface with data unsaved Battery type Four battery types are preset which are GEL SLD FLD and USr Only parameters of USr type are adjustable Controller communication SN composed of 8 digits every 2 digits displayed sequentially eg 88 56 73 24 a long pressing 3 S enables data saving and exit and a 20s absence of operation bring you to main loop...

Page 23: ...estart charging Symptoms Checks No sign on LCD initialization Make sure no reverse connected battery and connection between battery and controller is good make sure circuit of battery switched on and fuse protector connected No charging current Make sure no reverse connected solar panel and connection between solar panel and controller is good with no open circuit Load not work Make sure ther s no...

Page 24: ...ngle of the PV panel change the location of M8 bolts in the arc hole of the tilt arms Remember to use lock washers to prevent vibration from working them loose Step4 For pole mounting use hose clamps not included to fix the PV module and mount assembly securely to the pole See figure 2 The U Bolts Steel Clamps and Molly Bolts are not included in the kit www solarland com info solarland com Tel 86 ...

Page 25: ...t Fig 6 IT Cablaggio Esempio con centralina CT10224 EN Wiring Example with CT10224 Control unit IT NON UTILIZZARE MAI IL PANNELLO SO LARE E IL TRASFOR MATORE AC ALLO STESSO TEMPO NON COLLEGARE IL CAVO 2 NEL CONNET TORE DELLA BAT TERIA COLLEGARE SOLO ALL ALIMENTA ZIONE EN NEVER USE THE SOLAR PANEL AND THE AC TRANSFOR MER AT THE SAME TIME DO NOT CONNECT CABLE 2 INTO BATTE RY CONNECTOR ONLY CONNECT T...

Page 26: ...M SUDAN 4 KINSHASA NDJILI ZAIRE 4 KINSHASA NDOLO ZAIRE 0 KISANGANI ZAIRE 6 LAGOS NIGERIA 28 PALMAS DE GC 10 LINDI TANZANIA 12 LOBITO 6 LOME TOGO 11 LUBUMBASHI ZAIRE 26 LUDERITZ SOUTH AFRICA 4 LUZAMBA ANGOLA 25 MAPUTO MOZAMBIQUE 29 MASERU LESOTHO 1 MBALA ZAMBIA 2 MOGADISHU SOMALIA 6 MONROVIA LIBERIA 7 MWANZA TANZANIA 12 NDJAMENA CHAD 1 NAIROBI KENYA 1 NAIROBI KENYA 15 NAMIBE ANGOLA 18 NOUAKCHOTT MA...

Page 27: ...ESTER PA 42 LANSING MI 27 LAREDO TX 36 LAS VEGAS NV 42 LAWRENCE MA 38 LEXINGTON KY 40 LIMA OH 41 LINCOLN NE 34 LITTLE ROCK AR 34 LOS ANGELES CA 38 LOUISVILLE KY 42 LOWELL ME 33 LUBBOCK TX 33 MACON GA 43 MADISON WI 43 MANCHESTER NH 32 MARSHALL TX 35 MEMPHIS TN 41 MERIDEN CT 26 MIAMI FL 43 MILWAUKEE WI 45 MINNEAPOLIS MN 48 MINOT ND 30 MOBILE AL 32 MONTGOMERY AL 44 MONTPELLIER VT 40 MUNCIE IN 36 NASH...

Page 28: ...Key Automation S r l Via Meucci 30027 San Donà di Piave VE T 39 0421 307 456 F 39 0421 656 98 info keyautomation it www keyautomation it Instruction version 580SOLAR REV 03 ...

Reviews: