7
ENGLISH
5.4 TERMINAL BOARD J6 – OPENING AND CLOSING TRAVEL LIMIT DEVICE
Terminal board for connection of the opening (FCA and FCA2)
and closing (FCC and FCC2) travel limit device.
The travel limit contacts FCC1, FCA1, FCC2
and FCA2 are all NC contacts. See 2nd level
programming for the various configurations
applicable to the travel limit inputs.
If they are not used, do not jumper connect the contacts
of the limit switches FCC1, FCA1, FCC2, FCA2
5.5 TERMINAL BOARDS J7 - ENCODERS
Encoders with an open collector signal referred to earth (e.g.
Gatecoder) can be connected to detect the leaf’s angular
position. For connections, see fig. 0.
The configuration indicated in the drawing is
the maximum one. Only 1 Gatecoder can be
used. In this case, the unused inputs do not
have to be jumper connected to earth
The default obstacle detection and stop point
times are 2 and 4 seconds respectively.
RED
RED
BLACK
BLACK
WHITE
WHITE
5.6 TERMINAL BOARD J9 – FLASHING LAMP
Output for 24Vdc flashing lamp
Maximum applicable load: 24 Vdc - 15 W
5.7 TERMINAL BOARD J10 – ELECTRIC LOCK
Output for 2V ac or 24V dc electric lock
5.8 TERMINAL BOARD J11, J12 - MOTORS
J11 (MOT1)
: Connection of motor connected to leaf , i.e. the
leaf which opens first during an opening operation.
J12 (MOT2)
: Connection of the motor connected to leaf 2,
i.e. the leaf which opens second.
If only one motor is connected, it must be
connected to terminal J11 (MOT1).
If, during the first movement of the SETUP
procedure, the leaves open instead of closing,
the motor connection cables must be changed
over.
5.9 CONNECTOR J1 - PRIMARY POWER FEED FROM
230/115 V MAINS
J1:
Select the correct power feed, by turning the power switching
selector to its correct position (Default 230 Vac.)
To ensure correct operation, the switching
feeder must be connected to the earth
conductor in the system. Install an adequate
differential thermal breaker upstream of the
system.
Fig. 0
115 Vac
Fig.
230 Vac