6.2 OPERATING LOGICS
In all the logics:
- the
STOP
command has the priority and stops the
automation system from working
- the
EMERGENCY
command has the priority and opens
the automation system.
EP
- SEMI-AUTOMATIC STEP BY STEP
The
EP
logic requires the use of just the
OPEN
com-
mand:
-
OPEN
when the barrier is closed, it commands the
opening.
-
OPEN
when the barrier is open it commands the
closing.
-
OPEN
during the movement it stops
-
OPEN
after the stop, it reverses in movement.
The
CLOSE
command always commands the closing.
A
- AUTOMATIC
Logic
A
only requires the
OPEN
command:
-
OPEN
when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN
when the barrier is open in pause mode, it
reloads the pause time. (Even the intervention of
the photocells reloads the pause time)
-
OPEN
during opening is ignored.
-
OPEN
during opening causes it to open again.
The
CLOSE
command always commands the closing.
AP
- AUTOMATIC STEP-BY-STEP
The
AP
logic requires the use of just the
OPEN
com-
mand:
-
OPEN
when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN
when the barrier is open in pause mode it
locks. (Even the intervention of the photocells
during the pause mode reloads the pause time)
-
OPEN
during the opening locks.
-
OPEN
during opening causes it to open again.
The
CLOSE
command always commands the closing.
b
- SEMI-AUTOMATIC B
Logic
b
requires the use of the
OPEN
and
CLOSE
commands:
-
OPEN
when the barrier is closed, it commands the
opening.
-
CLOSE
when the barrier is open it commands the
closing.
-
CLOSE
during opening it causes reclosing.
-
OPEN
during opening causes it to open again.
bC
- SEMIAUTOMATIC
b
ON OPENING/ PERSON
PRESENT
C
ON CLOSING
bC
logic requires the use of the
OPEN
command on
opening and
CLOSE
maintained on closing. The
activation of the
CLOSE
command on closing must be
intentional and the barrier must be visible.
-
OPEN
when the barrier is closed, it commands the
opening.
-
Maintained
CLOSE
commands the closing.
C
- DEAD-MAN
Logic
C
requires the use of maintained
OPEN
and
CLOSE
commands. The control must be activated
intentionally and the barrier must be visible.
-
Maintained
OPEN
commands the opening.
-
Maintained
CLOSE
commands the closing.
-
If the photocells are triggered, movement is
stopped.
P
- PARKING
Logic
P
requires the use of the
OPEN
and
CLOSE
commands:
-
OPEN
when the barrier is closed, it commands the
opening.
-
CLOSE
when the barrier is open it commands the
closing.
-
CLOSE
during opening it causes reclosing after
opening.
-
OPEN
during opening causes it to open again.
-
The triggering of the photocells during closing
stops the movement, on disengagement the barrier
continues to close.
PA
- PARKING AUTOMATIC
Logic
PA
requires the
OPEN
and
CLOSE
commands
to be used.
-
OPEN
when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN
when the barrier is open in pause mode, it
reloads the pause time. (Even the intervention of
the photocells reloads the pause time)
-
CLOSE
when the barrier is open it commands the
closing.
-
CLOSE
during opening it causes reclosing after
opening.
-
OPEN
during opening causes it to open again.
-
The triggering of the photocells during closing
stops the movement, on disengagement the barrier
continues to close.