background image

• 

E (semi-automatic): This mode requires a 
command to open and a command to close.  

A second command during opening stops the 

gate.  A second command during closing 

reopens the gate. 

 

• 

EP (semi-automatic, step by step): This mode 
requires a command to open and a command 

to close. A second command during opening 

or closing causes the gate to stop. A third 

command then reverses the previous motion 

of the gate. 

 

• 

B (manned, pulsed):  This  mode  is  designed 
for guard station use and requires a three-

button switch (pulsed) to open, close, and 

stop the gate. 

 

• 

C (manned and constant): This mode requires 
constant pressure switches. One to open and 

one to close. No pressure on a switch stops 

the gate. 

 

The three programming push buttons allow the 

programming of the torque (or pressure), the pause 

time between opening and closing, and the leaf delay 

on closing. 

 

WARNING! Turn the main power off before you 

make any electrical connections. 

 

For all FAAC hydraulic operators using the 455 D 

control panel, the force must be set at its maximum 

setting of 50 in order to supply the correct voltage to 

the operator.   

 

P

AUSE

  T

IME

:  The pause time between opening and 

closing can be adjusted from 0 seconds to 4 minutes.  

Time is adjusted in one-second increments from 0—

59 seconds.  When 60 seconds is reached, time is 

adjusted in 10 second increments up to 4 minutes.  

i.e. if display shows 2.5, it means 2 minutes and 50 

seconds. 

 

L

EAF

  D

ELAY

:  You may choose to delay one leaf on 

closing for overlapping gate leaves. Be sure the 

operator on the leaf for delayed closing is connected 

to Motor 1. On opening, the leaf connected to Motor 2 

is delayed 2.5 sec.  

 

N

OTE

: If an opening leaf delay is desired, it must 

be enabled in the Advance Programming. 

 

However, if enabled, you cannot 

adjust

 this 

opening delay of the operator connected to 

Motor 2.  

 

The closing leaf-delay time is adjustable from 0 to 4 

minutes.  

 

N

OTE

: If the opening/closing time is set at less 

than the leaf delay time, the delayed leaf closes 

at the end of the closing time. 

Page 18 

November, 2003 

400 Operator And  

455 D Control Panel Installation Manual  

opening and closing, respectively, are triggered. Use 

the LEDs and the next table to determine if the 

accessory devices you have installed are operating 

properly. 

 

Electric Locks: An electric lock can be wired to the 455 

D in terminals 18 and 21 (12Vac pulsed provided). If a 

reversing stroke is needed to allow the electric lock to 

release, this must be done in advanced programming. 

 

See page 19 for the connections for a magnetic 

locking device. 

 

W

ARNING

  L

IGHT

: Connect a warning light to 

terminals 18 and 20 in the group labeled 

W.LIGHT

 

in terminal block J1 and J5. The terminals provide 

an output voltage of 24 VDC, maximum power 3 

Watts. This output voltage will power most 24 VDC 

warning lights. 

 

N

OTE

: The behavior of the warning light varies 

according to the logic you have set. 

 

L

OGICS

  A,  S,  E,  EP, 

AND

  B: The warning light is on 

steadily during opening and the pause phase. During 

closing, the light flashes. 

 

L

OGIC

  C: The warning light is on steadily during 

opening and flashes during closing. 

 

 

S

ET

 O

THER

 O

PERATING

 C

ONTROLS

 

 

WARNING! Turn the main power off before you 

make any electrical connections. 

 

You need to program the control panel for your gate's 

operation. The 455 D Control Panel has on board 

programming that controls a wide range of functions. 

 

O

PERATING

 L

OGICS

 

 

N

OTE

: The 455 D Control Panel provides inputs 

for opening reversing devices and closing 

reversing devices. FAAC strongly recommends 

the use of reversing devices, such as photocells 

or other non-contact sensors. 

 

• 

A (automatic): The gate opens on command 
and automatically closes after a pause phase. A 

second command while opening is ignored; a 

second command during the pause phase 

interrupts the pause time; a second command 

during closing reopens the gate.  A maintained 

open command  will hold the gate open. 

 

• 

S (security):  The  security  mode  is  like  A  logic 
except that a second command during opening 

immediately closes the gate.  A maintained 

open command will not hold the gate open. 

T

HE

 455 D C

ON

T

R

OL

 P

ANEL

 I

NS

TA

LL

ATIO

N

 I

N

STR

U

C

TI

O

N

S

 

Summary of Contents for 455 D

Page 1: ...455 D Control Panel General Description 14 Installing the 455 D Control Panel 14 Connect the Main Power Supply 14 Connect the Operator to the Control Panel 15 Check the Motor s Direction of Rotation 1...

Page 2: ...ons before the automatic operator is installed 4 An automatic operator should be installed on the inside of the property fence line Do not install the operator on the public side of the property fence...

Page 3: ...mproper and therefore dangerous 2 When using any electrical equipment observe some fundamental rules Do not touch the equipment with damp or humid hands or feet Do not install or operate the equipment...

Page 4: ...ened and or closed Operator dimensions l w h in cm 40 X 3 5 16 X 3 5 16 102 X 8 5 X 8 5 47 1 2 X 3 5 16 X 3 5 16 121 X 3 X 8 5 Operator weight lb kg 19 8 6 Power voltage required VAC7 115 VAC 10 60 Hz...

Page 5: ...luded see Figure 1 If you have ordered a kit a pair of operators you will have twice the quantity of parts listed below except where noted and you will also have a radio receiver and two transmitters...

Page 6: ...h the 400 Operator The Manual Release mechanism is a key operated device that disengages or engages the hydraulic system of the 400 Operator When the hydraulic system is disengaged you can open and cl...

Page 7: ...g steps 1 Attach the rear mounting bracket 2 Attach the mounting hardware 3 Attach the front mounting bracket 4 Attach the operator to the gate 5 Adjust the operator pressure ATTACH THE REAR MOUNTING...

Page 8: ...ately 6mm Note Be sure that the operator is level and that the gate is against the close positive stop Hold the front mounting bracket flush against the gate Mark the location of the front mounting br...

Page 9: ...RNING The piston should not bottom out in either direction Doing so will seriously damage the operator Be sure that the gate reaches the positive stop before the piston bottoms out Adjust the swivel j...

Page 10: ...ate the control panel in the most convenient position possible considering the movement of the gate Figure 7 shows a basic layout for a two leaf gate with the 400 Operator Installing the control panel...

Page 11: ...the 400 operator should bleed itself Running the operator should remove any air from the system If the operator runs smooth throughout the swing no attempt to further bleed the unit is necessary If t...

Page 12: ...Page 12 November 2003 400 Operator And 455 D Control Panel Installation Manual EXPLODED VIEW 400 CBAC...

Page 13: ...2 36 7039025 Washer Swivel 1 37 702201 Swivel Jam Nut 10mm 1 38 7073025 Swivel Joint 1 39 N A Star Washer 5mm 2 POS PART NO DESCRIPTION QTY 40 7119405 Protective Cover End Cap Plug 2 41 7019195 Tie Ro...

Page 14: ...cal codes The installer should refer to the installation manual for a given operator for more information NOTE An installation is U L compliant only when you install the FAAC operators according to th...

Page 15: ...eaf gate design be sure to connect its operator to Motor 1 In order to wire motor 2 in a bi parting system connect the white wire to terminal 4 on the J4 terminal strip the black wire to 5 the red wir...

Page 16: ...ain power and send an activating signal to the operator The gate leaf or leaves should open If a gate leaf closes then you need to turn off the main power and reverse the connection of the red and bla...

Page 17: ...he respective terminals OP_A and OP_B Partial Opening should illuminate only when an activating signal is sent for 2 and 1 gate leaves respectively STOP should be illuminated except when the stop butt...

Page 18: ...he delayed leaf closes at the end of the closing time Page 18 November 2003 400 Operator And 455 D Control Panel Installation Manual opening and closing respectively are triggered Use the LEDs and the...

Page 19: ...17 Additional Reversing Devices TX RX 1 2 1 2 3 4 5 19 17 12 19 17 Additional Reversing Devices TX RX 1 2 19 12 17 15 Additional Reversing Devices 8 7 Saf ety Loop Detector f or closing 1 2 3 4 5 RX 1...

Page 20: ...the value that can be modified with keys and When you reach the last function press the F key to exit the program and the display resumes showing the status of the inputs The table on page 9 shows the...

Page 21: ...ns as a standard indicator light lighted at opening and pause flashing at closing and off when gate closed Different figures correspond to timed activation of the output which can be used via a relay...

Page 22: ...leaves begin the opening movement The movement stops automatically when the opening positive stop is reached and the display stops flashing LEARNING OF OPERATING TIMES WARNING During the learning pro...

Page 23: ...e gate operator reaches its positive stop the operator will automatically shut off An open command must be given to start closing gate operator 2 When gate operator 2 reaches the position that you wan...

Page 24: ...g Reversing Device s Warning Light Closed Opens both leaves and closes them after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Ope...

Page 25: ...ens single leaf connected to Motor 1 No effect opening is in hibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device...

Page 26: ...tential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fast the gate operates The operator you choose to install on your gate must be desig...

Page 27: ...your reversing devices If no reversing devices are installed make sure a circuit is installed between appropriate terminals PROBLEM THE GATE DOES NOT FULLY OPEN OR CLOSE SOLUTION Increase the bypass...

Page 28: ...or has been subject to misuse negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more sever...

Reviews: