Note that if chassis depth (L) is less than 40.64 cm (16 in.), the chassis will not fit into a rack with a maximum depth of 81.28 cm (32 in.)
using the universal four-post rack kit. The maximum rack depth for a chassis less than 40.64 cm (16 in.) is 81.28 cm (32 in.) minus the
difference between the chassis depth and 40.64 cm (16 in.). For example, a chassis with a depth (L) of 35.56 cm (14 in.) is 5.08 cm (2
in.) smaller than 40.64 cm (16 in.), so it will install into a rack with a maximum depth of 81.28 cm (32 in.) - 5.08 cm (2 in.) = 76.2 cm
(30 in.).
Observe the following when mounting this device:
•
Two people are required to install the device in a rack. One person holds the device, while the other screws in the front and rear
brackets.
•
Before mounting your device, review any specific installation and facility requirements in this Hardware Installation Guide.
•
Hardware devices illustrated in these procedures are only for reference and may not depict the device you are installing into the
rack.
Installation requirements
Provide space in an EIA rack with the following minimum and maximum distances between the front and back posts.
NOTE
For 1U and 2U devices, two people are required to install the device in a rack. One person holds the device, while the other
screws in the front and rear "L" brackets.
TABLE 10
Space requirements
Chassis with port-side
side vents
Notes
Chassis depth
Minimum rack depth
Maximum rack depth
No
Applicable to port-side and nonport-side flush
mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to port-side flush mounts.
L
L-12.7 cm (L-5 in.)
81.28 cm (32 in.)
Yes
Applicable to nonport-side flush mounts.
L
L
81.28 cm (32 in.)
Note that if chassis depth (L) is less than 40.64 cm (16 in.), the chassis will not fit into a rack with a maximum depth of 81.28 cm (32 in.)
using the universal four-post rack kit. The maximum rack depth for a chassis less than 40.64 cm (16 in.) is 81.28 cm (32 in.) minus the
difference between the chassis depth and 40.64 cm (16 in.). For example, a chassis with a depth (L) of 35.56 cm (14 in.) is 5.08 cm (2
in.) smaller than 40.64 cm (16 in.), so it will install into a rack with a maximum depth of 81.28 cm (32 in.) - 5.08 cm (2 in.) = 76.2 cm
(30 in.).
Review the installation and facility requirements for your product before mounting the device . Refer to the
Hardware Installation Guide
for your product for more information.
Time and items required
Allow 15 to 30 minutes to complete the installation.
The following items are required to install the device using the Universal Four-Post Rack Kit:
•
#2 Phillips torque screwdriver
•
1/4-inch slotted-blade torque screwdriver
Parts list
The following parts are provided with the Universal Four-Post Rack Kit (XEN-R000296).
Installing the Universal Four-Post Rack Kit (XEN-R000296)
ExtremeSwitching SLX 9030 Hardware Installation Guide
42
9035691-02 Rev AD
Summary of Contents for EN-SLX-9030-48S-4C
Page 6: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 6 9035691 02 Rev AD...
Page 10: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 10 9035691 02 Rev AD...
Page 64: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 64 9035691 02 Rev AD...
Page 76: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 76 9035691 02 Rev AD...
Page 82: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 82 9035691 02 Rev AD...
Page 96: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 96 9035691 02 Rev AD...