UK |
19
3112015_EBC22_UK
Overview of the service menu
The service menu is built up in four levels:
Base settings for the
three applications
Menu level 1
Menu level 2
Menu level 3
Function
Default
0 Exit
Service menu
Return to operation screen
1
Operation
settings
10 Exit operation
settings
11
Operating mode
Setting of control/operating
function
1 = Pressure-controlled regula
-
tion
2 = 2-stage speed regulation
3 = Supply air regulation
1
12 °C / °F
Select measuring unit for
temperature
1 = °C, 2 = °F
1 (°C)
1 (°C)
1 (°C)
13 Pa / inWC
Measuring unit for pressure:
1 = Pa, 2 = inWC
1 (Pa)
1 (Pa)
1 (Pa)
14
Software
versions
140 Exit
141
Controller
version
View Controller software version
x.xx
x.xx
x.xx
142
Safety version
View Safety software version
x.xx
x.xx
x.xx
143
Display version
View Display software version
x.xx
x.xx
x.xx
15 Select XTP mea
-
surement range
150 Exit
151 Set Low XTP
value
from -500 Pa to 0 Pa
0 Pa
N/A
0 Pa
152 Set High XTP
value
from 0 Pa to 500 Pa
150 Pa
N/A
150 Pa
16 Positive/negative
pressure
1 = negative pressure
2 = positive pressure
1
N/A
1
17
OEM functions
170 Exit
171
Cooker function
Switch Cooker function ON and
OFF
N/A
OFF
N/A
18
Reset to defaults
Reset to defaults. If you select
“YES”, a
10-second countdown will start,
during which you can cancel your
choice by pressing any button.
NO
NO
NO
2
Alarm
20 Exit Alarm
21
Alarm Log
210 Exit
211 -219
The 9 most recent alarms
22
Reset alarm log
Resets alarm log
NO
NO
NO
23
Flow Alarm limit
Set Flow Alarm limit in %:
: 50-80% ( Alarm when
pressure is below xx% )
: 100-300% ( Alarm when
pressure is above xx% )
64%
N/A
300%
24
Flow Alarm delay
Set Flow Alarm delay, 10–60 s
15 s
15 s
15 s
25
Reset auto /
manual
1 = automatic, 2 = manual
1 Auto)
1
(Auto)
11
(Auto)