20
| UK
Your energy.
Optimized.
Base settings for the
three applications
Menu level 1
Menu level 2
Menu level 3
Function
Default
3 Configuration
30 Exit settings
31 PDS/AUX config
1 = PDS, 2 = C-NO
2 (C-NO) 1 (PDS)
(Locked) 2 (C-NO)
32
Triac settings
320 Exit
321
Umin
Min. output voltage in % of 230V
AC, 35-100%
35%
N/A
35%
322 Umax
Max. output voltage in % of 230V
AC, 35-100%
100%
N/A
100%
33 0–10V settings
330 Exit
331
Umin
Min. output voltage in % of 10V
DC, 0-100%
0%
N/A
0%
332 Umax
Max. output voltage in % of 10V
DC, 0-100%
100%
N/A
100%
34
Manual Fan
mode
340 Exit
341
Manual Fan
mode on/off
Switch Manual Fan mode on and
off
OFF
OFF
OFF
342
Manual Fan
mode speed
Set the motor manually,
35–100%
35%
35%
35%
35
Regulation
parameters
350 Exit
351 Amplification Xp Set proportional amplification,
0.2 to 5
2,2
N/A
1,2
352
Integration time
Ti
Set integration time from 1 to
30 s
5
N/A
3
353
Differential time
Td
Set differential time from 1 to
30 s
1
N/A
5
354
Sample time
Set sample time from 1 to 999
ms
300 ms
N/A
300 ms
4 Temp. sensor
40 Exit Temp. sensor
41
Sensor ON/OFF
turn temperature sensor ON/OFF OFF
OFF
42
Auto Start/Stop
420 Exit
421
ON/OFF
turn temperature sensor ON/OFF OFF
OFF
422
Start
temperature
select start temperature in 5–450
°C range
40 °C
40 °C
423
Stop
temperature
select stop temperature in 0–445
°C range
35 °C
35 °C
43
Forced operation
430 Exit
431
ON/OFF
turn forced operation ON/OFF
OFF
OFF
432
Limit
temperature
select temperature limit in 5–450
°C range
250 °C
50 °C
44
Alarm
440 Exit
441
ON/OFF
turn alarm ON/OFF
OFF
OFF
442
Limit
temperature
select temperature limit in
25–450 °C range
450 °C
450 °C
443
Alarm delay
Select delay-length of limit
temperature alarm: 0–60 second
range
5
5
Summary of Contents for EBC22