Single- or two boiler application
This example shows how to connect a voltage signal (10–230V AC/DC) for the EBC22 to start/stop the
fan from one or two independent boilers
•
Connect the supply voltage to terminals 1–3
•
Connecting the boilers:
•
Connect the burner start signal (L) to terminal 11 & 15
•
Connect the neutral wire to terminal 12 & 16
•
The start signal for the burner is sent from terminal 14 & 18
•
Loop terminals 11 and 13
•
Loop terminals 15 and 17
•
Connect the chimney fan to terminals 4–6
•
Connect the pressure transducer (XTP) to terminals 23–28