UK |
39
3112015_EBC22_UK
User menu
Layout of the user menu
The user menu consists of a single level and provides access to 4 parameters:
Menu Function
Range
1
Setting the required pressure
Depending on the XTP-range set in menus 151 and 152
2
Setting the pre-purge period for the fan
0-999 s
3
Setting the post-purge period for the fan
0-60 min
4
Displaying current alarm (see alarm overview page 34)
-
When the instructions refer to the menu numbers 1, 2, 3 and 4 it is understood that these numbers refer to the user menus.
Operating the user menu
Before you can use the EBC22 for pressure controlled regulation of Exodraft supply air fans, you will have
to change the operating function.
For setting up the operating function, see page 22.
Using the buttons
Step
Press...
To...
1
Activate the user menu
2
and
Go to the menu item you wish to edit
3
Edit the menu item selected
4
and
Adjust the required set point
5
Confirm the required set point
6
To save the required set point: Press
again within 5 seconds
7
Return to operation screen.
NB: If you do not press
the EBC22 will automatically return to the operation screen after 30 sec.
You can always undo an action (that you have not confirmed by pressing
) and return to the operation screen by pressing
Adjust the set points for user menu items 1–4 as shown in the example on the following page.
Alarms
For alarm handling (menu 5), see page 41-42
Commissioning should be carried out by staff with the appropriate training, and with the authorisation
to do so according to local legislation.