2.4.6
Solid fuel boiler with temperature sensor
The example shows how to connect the temperature sensor to the EBC20 in order to stop and start the fan through
the temperature in the chimney
• Connect the supply voltage to terminals 1–3.
• Connecting the boiler:
Connect the burner start signal (L) to terminal 11.
Connect the neutral wire to terminal 12.
Loop terminals 11 and 13.
The start signal from the burner comes from terminal 14.
• Connect the ventilator to terminals 4 and 6.
• Connect the pressure transducer (XTP) to terminals 23 and 25.
• Using a junction box connect the temperature sensor to terminals 29 and 31.
• Set menu 41 to ”ON”. Other settings should be chosen from menu 4.
3002878-EBC20-UK
22
• Pressure control