2.4.2
Single boiler application with potential free contact in boiler
This example shows how to connect a potential free contact to the EBC20 to start/stop the fan:
• Connect the supply voltage to terminals 1–3
• Connection to the boiler:
Connect the potential free contact to terminals 11 & 19
Loop terminals 12 & 20
Connect the burner start signal to terminals 13 & 14
• Connect the chimney fan to terminals 4–6
• Connect the pressure transducer (XTP) to terminals 23–25 using a a shielded
cable 3x0,75 mm
2
and connect the cable shielding to the cable bracket
3002878-EBC20-UK
18
• Pressure control