Curtiss-Wright | TRITEX II AC 75 Rev. K PN61928 7/12/2022
53
Analog Input
An analog input is provided for use as a position, velocity or
current command.
Differential input range is -10 V to +10 V. Input range on Analog IN+ is
-15 V to +15 V with respect to IO Common. Input range of Analog IN- is
-15 V to +12 V with respect to IO Common. The analog signal must be
wired differentially with a return wire to the analog signal source for best
noise rejection.
(See software section for configuration of the analog input and
analog motion parameters.)
Analog Input Wiring from External Controller
Note: Analog input reference from an external controller must be
referenced to single point ground to prevent damage to the analog input
circuit.
Analog Input Specifications
Description
Specification
Voltage Input Range
-10 V to +10 V
Input impedance
100 k
Ω
Input resolution
13 bits over full -10 V to +10 V range
Update rate
0.5 ms
Summary of Contents for Curtiss-Wright Tritex II Series
Page 10: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 9 UL Certificate of Compliance...
Page 11: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 10...
Page 14: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 13...
Page 15: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 14...
Page 18: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 17...
Page 19: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 18...
Page 74: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 73 T2IPC xxx Power Cable...
Page 75: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 74 TTICO xxx Communications Cable...
Page 77: ...Curtiss Wright TRITEX II AC 75 Rev K PN61928 7 12 2022 76 Braking Resistor T2BR1...