3704-IG-001 Installation and User Manual
Page 12
Wall-Mounting Options
There are 4 mounting-screw holes in the rear mounting assembly of the 3704 EVSE, two at the top and two at the bottom.
Using the mounting hole pattern depicted (Figure 5), drill pilot holes if necessary. The mounting hardware/holes should be
designed around #10-sized screws. Ensure the hole pattern is plumb and level. NOTE – Conduit(s) enters through the bottom-
center, conduit-access hole.
NOTE: In order to remain ADA-compliant, from the user’s perspective, the center of the 3704’s Data Router MUST be no
more than 48 inches from the ground when mounted to the pole, regardless of how the pole is mounted to the
ground, or to a wall (Figure 1B).
Optional AC power access
hole for wires brought
through the wall
Figure 5
Optional Serial Communication
access hole for wires brought
through the wall