3704-IG-001 Installation and User Manual
Page 13
Electrical Service Connections
(
DUAL UNIT SHOWN
)
Note: Observe all required Lockout/Tagout procedures while making any electrical connections or servicing the Model 3704.
Caution:
The two phases used must each measure
120V to Neutral. Earth Ground must be
connected to Neutral at only one point,
usually at the Service Entry Breaker Panel.
Caution:
This EVSE is a single-phase device. Do not connect
all 3 phases of a 3-phase feed!!! You may use any
two phases of a 3-phase, Wye-connected feed !
The center-point of the 3 phases (usually used as
Neutral) must be grounded somewhere in the
system. A current-carrying Neutral is not needed by
the Model 3704. The two phases used must each
measure 120V to Neutral.
1)
220/240 VAC, Single Phase Transformer
:
2) 208 VAC 3-Phase Wye Transformer:
Note: A separate 40 Amp. Non-GFCI breaker is required for each individual EVSE.
Model 3704
Figure 6A
Figure 9B
(See
Fig. 7B)
Attention:
Les deux phases utilisés doivent
chaque 120V mesure au Neutre.
Motif de la terre doit être connecté
au Neutre à un seul point,
habituellement à l'entrée de
Service Breaker Panel.
Attention:
Cette EVSE est un appareil monophasé. Ne pas
connecter tous les 3 phases d'un flux de phase 3!!!
Vous pouvez utiliser tout deux phases d'une phase
3, Wye connecté nourrir ! Le point central des 3
phases (généralement utilisé comme Neutre) doit
reposer quelque part dans le système. Il n'est pas
nécessaire de Neutre porteurs de courant par le
Modèle 3704. Les deux phases utilisés doivent
chaque 120V mesure au Neutre.
Model 3704
Figure 6B