SFC SC
Description
3.
13
Interfaces
Display and operating unit
Relay outputs
Digital inputs
2x inputs for voltage-free contact (< 100 Ohm) power supply
via SFC SC (12 V)
DI 1: Sample water monitoring / freely selectable in menu
DI 2: Freely selectable in menu
Measurement inputs
1 x Feedback input
Positioner position feedback
Potentiometer 1 kOhm or 5 kOhm, 0 – 1 V, 0 – 20 mA
(selectable using DIP switches)
1x mA input for flow rate 0 – 20 mA/4 – 20 mA
In SFC units with a 24 V supply voltage this input is not
electrically isolated from the 24 V DC supply voltage.
1x RS232 for firmware updates (not galvanically isolated)
1 x Operating panel with 9 keys
1 x Graphic display:
• Resolution 128 x 64 pixels
• white background illumination
2 relay outputs (2 two-way switches)
Switching values
5 A, 250 V AC, 1250 VA max
5 A, 220 V DC, 150 W max
UL/CSA-rating
5 A, 1/6 HP 125, 250 V AC
5 A, 30 V DC, 30 W max
1 A, 30 V DC - 0.24 A, 125 V DC
Summary of Contents for WALLACE & TIERNAN SFC SC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC SC from version V 3 06 INSTRUCTION MANUAL ...
Page 2: ...2 WT 050 590 020 DE IM 0719 SFC SC Please note Original manual ...
Page 18: ...18 WT 050 590 020 DE IM 0719 Description SFC SC 3 ...
Page 42: ...42 WT 050 590 020 DE IM 0719 Installation SFC SC 5 ...
Page 66: ...66 WT 050 590 020 DE IM 0719 Maintenance SFC SC 7 ...
Page 72: ...72 WT 050 590 020 DE IM 0719 Wiring Diagrams SFC SC 9 ...
Page 73: ...SFC SC Certificats 10 73 10 Certificats ...
Page 74: ...74 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...
Page 75: ...SFC SC Certificats 10 75 ...
Page 76: ...76 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...