SFC SC
Functions
4.
25
4.4
Controller outputs
Controller types
Positioner (with feedback)
By selecting the positioner it is also possible to perform chlorine
feed in combination with a positioner that operates as an actuator
in a chlorinator.
If positioner feedback is available, it must be calibrated during
commissioning. Potentiometer 1 KOhm/5 KOhm or 0 – 1 V or 0/
4 – 20 mA signals can be connected as positioner feedback (see
section 4.7 “Actuator feedback”). It is possible to linearize the
actuator using several calibration points.
2-point pulse
length controller
for dosing pumps
The dosing pump is switched on for the calculated time within an
adjustable cycle period TP (relay contact). The cycle period is
mainly determined by the reaction time of the connected system
and entered as the cycle period TP.
Controller for
Type
Parameter
description
Action
Positioner with feedback
3-point
Positioner with Ym
Dosing
or
Motor dosing pump (pulse duration
controller)
2-point
Dosing pump 2p
Dosing
or
Pulse pump (pulse frequency controller)
2-point
Pulse pump 2p
Dosing
or
Dosing pump with mA-input
2-point
Analog output 2p
Dosing
or
Example:
Cycle period TP
=
100 s
Output value Yout
=
30 %
Duty cycle
30 s
Off duty cycle
70 s
Summary of Contents for WALLACE & TIERNAN SFC SC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC SC from version V 3 06 INSTRUCTION MANUAL ...
Page 2: ...2 WT 050 590 020 DE IM 0719 SFC SC Please note Original manual ...
Page 18: ...18 WT 050 590 020 DE IM 0719 Description SFC SC 3 ...
Page 42: ...42 WT 050 590 020 DE IM 0719 Installation SFC SC 5 ...
Page 66: ...66 WT 050 590 020 DE IM 0719 Maintenance SFC SC 7 ...
Page 72: ...72 WT 050 590 020 DE IM 0719 Wiring Diagrams SFC SC 9 ...
Page 73: ...SFC SC Certificats 10 73 10 Certificats ...
Page 74: ...74 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...
Page 75: ...SFC SC Certificats 10 75 ...
Page 76: ...76 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...