Functions
SFC SC
4.
The relationship between the flow control variable and the dosing
output is determined using the internal dosing factor. This can be
varied up to max. 400%.
If a positioner with feedback is used as the dosing output, it can be
linearized using several support points. At least two points are
required (0/100 %). It possible to define 2, 3, 6 or 11 support points
with definite steps. In the menu„Dosing“ - „Ym Calib. Points“ it is
possible to set the number of points used. The support points then
have to be set in menu „Dosing“ - „Ym Calib.Manual“ (see 5.3.5
“Positioner calibration”).
The controller output is calculated in this operating mode as
follows:
Yout = Wq x DF
Wq
Control variable 1 flow in %
DF
Set dosing factor in %
The figure below shows the output dosing capacity depending on
the flow rate Wq and the set dosing factor.
Picture 4
Dosing factors
Y o u t
1 0 0 %
1 0 0 %
W q
5 0 %
d o s i n g f a c t o r D i = 2 0 0 %
d o s i n g f a c t o r D i = 1 0 0 %
d o s i n g f a c t o r D i = 5 0 %
Summary of Contents for WALLACE & TIERNAN SFC SC
Page 1: ...WALLACE TIERNAN MEASURING AND CONTROL SYSTEM SFC SC from version V 3 06 INSTRUCTION MANUAL ...
Page 2: ...2 WT 050 590 020 DE IM 0719 SFC SC Please note Original manual ...
Page 18: ...18 WT 050 590 020 DE IM 0719 Description SFC SC 3 ...
Page 42: ...42 WT 050 590 020 DE IM 0719 Installation SFC SC 5 ...
Page 66: ...66 WT 050 590 020 DE IM 0719 Maintenance SFC SC 7 ...
Page 72: ...72 WT 050 590 020 DE IM 0719 Wiring Diagrams SFC SC 9 ...
Page 73: ...SFC SC Certificats 10 73 10 Certificats ...
Page 74: ...74 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...
Page 75: ...SFC SC Certificats 10 75 ...
Page 76: ...76 WT 050 590 020 DE IM 0719 Certificats SFC SC 10 ...