66
WT.090.370.000.DE.IM.0715
Operation
Barrier M
5.
5.3
Service life of UV lamps
The number and type of the lamps installed can be laid out accor-
ding to the flow rate and the condition of the water to be treated.
The UV lamps are wear parts. The operating life of the UV lamps
is normally up to about 9,000 hours, provided that the UV disinfec-
tion unit is operated according the described operating conditions
that are defined in the setting data configuration sheet on page 2
of the operating manual.
Primarily, this includes the following factors:
•
Operation in disinfection control mode (standard)
•
stable flow rate
•
stable water quality (transmission T
10
, SSK)
•
non-adjustable alarm value for min. UV intensity
•
Switching operations (max. 4 per day)