Please note
The respective error messages are shown as text messages on
the display depending on what screen the unit currently has open.
Cleaning active
The LED "CLEANING" lights up green
when the automatic cleaning mechanism is
active.
Cleaning alarm
The LED "CLEANING" lights up red if the
automatic cleaning mechanism is faulty.
The lamp(s) is/are automatically switched
off and a voltage-free contact is activated.
The green LED "UV
" disappears.
Lamp … active
The number of lamps used varies between
1 and 6, depending on the unit configura-
tion.
The green LED lights up when the respec-
tive lamp is active.
UV lamp failure
The green LED flashes when the respec-
tive lamp failed. A voltage-free contact is
activated at the same time. Optionally, the
other lamps can also be switched off at the
same time (optional time delay). As soon
as the UV value is fallen below the alarm
value the green LED „UV
“ disappears
and the LED „UV
“ lights up red.
Summary of Contents for WALLACE & TIERNAN Barrier M 1200
Page 1: ...WALLACE TIERNAN UV DISINFECTION UNIT BARRIER M OPERATING MANUAL...
Page 2: ...2 WT 090 370 000 DE IM 0715 Barrier M Please note Original manual...
Page 96: ...96 WT 090 370 000 DE IM 0715 Spare parts maintenance schedule Barrier M 6...
Page 100: ...100 WT 090 370 000 DE IM 0715 Table of UV alarm levels Barrier M 7...
Page 102: ...102 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 103: ...Barrier M Certificates declarations and statements 8 103 8 2 QPS certificate...
Page 104: ...104 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 105: ...Barrier M Certificates declarations and statements 8 105 8 3 NSF certficate...
Page 106: ...106 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Page 109: ...Barrier M 109...