14. Upload the “*.bin” file supplied using the X-Modem transfer protocol of your terminal program. If
you do not start the upload within 10 minutes the unit’s Boot code will time out. You can restart the
upgrade process by power cycling the unit.
If you are upgrading the main 5600MSC application firmware the bin file will have a name
something like
5600MSC.bin
There are two different versions of HD test generator cards that may be installed in the 5600MSC.
The front panel will show the version that is installed. Make sure that you upload the correct
version for your unit.
If you are upgrading the 7750TG2-HD Test generator application firmware the bin file will have a
name something like
7750TG2-HD.bin
If you are upgrading the 7751TG2-HD Test generator application firmware the bin file will have a
name something like
7751TG2-HD.bin
15. The boot code will indicate whether the operation was successful upon completion of the upload.
For Example:
UPLOAD OKAY
MFC5407 WARM BOOT> |
16. The following is a list of possible reasons for a failed upload:
•
If you get the message "transfer cancelled by remote" you must restart the terminal program and
load the bin file, then remove and install the module again.
•
The supplied “*.bin” file is corrupt.
•
Wrong file specified to be uploaded.
•
Wrong file transfer protocol used – make sure you specify Xmodem, not Xmodem 1K.
•
The PCs’ RS-232 communications port can’t handle a port speed of 57600.
•
Noise induced into the Serial Upgrade cable.
4.2.6. Completing the Upgrade
17. Power cycle the unit. The unit should now reboot.
18. You can now close the terminal program and disconnect the RS-232 serial cable from the PC.