EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 70 of 74
EV3K11
none
EVJ LCD none
Dry contact digital inputs (5 VDC, 1.5 mA)
Power supply: none
Protection: none
Minimum ON time for fast inputs to detect the pulse: 2.5 ms
Analogue outputs:
EV3 HRV
2 for 0-10 V/PWM/phase cutting
EVD HRV
EV3K11
none
EVJ LCD none
Analogue outputs 0-10 V (max. 10 mA)
Minimum load impedence:1 K
Ω
Resolution:
0.01 V
Protection: none
Phase cutting analogue outputs
Output:
10 VDC, max. 10 mA
Frequency: synchronised with that of the power supply
Pulse duration:
500 µs
Shift:
20... 90%
Protection: none
PWM analogue outputs
Output:
10 VDC, max. 10 mA
Frequency:
10... 2 KHz
Duty:
5... 95%
Protection: none
Frequency analogue outputs
Output:
10 VDC, max. 10 mA
Frequency:
10 Hz ... 255 Hz
Duty:
50%
Protection: none
Digital outputs:
EV3 HRV
Up to 6 outputs:
- 4 SPST relays, 3 A res. @ 250 VAC
- 1 200 mA triac res. @ 250 VAC at 25°C (77°F)
- 1 2 A triac res. @ 250 VAC at 25°C (77°F)
EVD HRV
Up to 5 outputs:
- 2 SPST relays, 3 A res. @ 250 VAC
- 1 SPST relay, 8 A res. @ 250 VAC
- 1 SPST relay, 12 A res. @ 250 VAC
- 1 open collector, 12 VDC, max. 40 mA
EV3K11
none
EVJ LCD none
Type 1 or Type 2 Actions
EV3 HRV
Type 1
EVD HRV
EV3K11
Not applicable
EVJ LCD Not applicable
Additional features of Type
EV3 HRV C