EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 43 of 74
Label
Default
value
Default
visibility
Min
Max
um
Description
I14
0
M
0
3
IN2 input type configuration
0 = NTC/Digital input
1 = 4-20 mA
2 = 0-10 V
3 = 0-5 V
I15
0
H
0
100
%
Start of humidity probe/remote control scale [@4mA/0V]
I16
100
M
0
100
%
End of humidity probe/remote control scale [@20mA/10V]
I17
0
M
-1,000
11,000
ppm-Pa
Start of CO
2
probe/pressure scale [@4mA/0V]
I18
2000
M
-1,000
11,000
ppm-Pa
End of CO
2
probe/pressure scale [@20mA/10V]
I19
0.0
M
-12.7
12.7
°C-°F-%-ppm-Pa
IN1 Analogue Input Offset
I20
0.0
M
-12.7
12.7
°C-°F-%-ppm-Pa
IN2 Analogue Input Offset
I21
0.0
M
-12.7
12.7
°C-°F
IN3 Analogue Input Offset
I22
0.0
M
-12.7
12.7
°C-°F
IN4 Analogue Input Offset
I23
0.0
M
-12.7
12.7
°C-°F
IN5 Analogue Input Offset
I24
0.0
M
-12.7
12.7
°C-°F
IN6 (EV3)/IN10 (EVD) analogue input offset
I25
0.0
M
-12.7
12.7
°C-°F
IN7 (EV3)/IN9 (EVD) analogue input offset
I26
5
M
-15
15
DO1 digital output function configuration
I27
6
M
-15
15
DO2 digital output function configuration
I28
12
M
-15
15
DO3 digital output function configuration
I29
7
M
-15
15
DO4 digital output function configuration
I30
0
M
-15
15
TK1 (EV3)/OC (EVD) digital output function configuration
I31
0
M
-15
15
TK2 digital output function configuration
I32
0
M
-15
15
AO1 digital output function configuration
I33
0
M
-15
15
AO2 digital output function configuration
I34
3
M
0
5
AO1 analogue output function configuration
I35
4
M
0
5
AO2 analogue output function configuration
I36
0
M
0
1
TK1 (EV3)/OC (EVD) analogue output function
configuration
I37
0
M
0
1
TK2 analogue output function configuration
I38
2
M
0
4
AO1 analogue output type configuration
I39
2
M
0
4
AO2 analogue output type configuration
I40
100
M
1
200
Hz*10
PWM Output Frequency
8.2
Configuring inputs
All the inputs can be configured by entering the appropriate values into parameters I01-I10. To configure a digital input, enter a value
less than 100; to configure an analogue input, enter a value equal to or greater than 100.
The value 0 indicates that no function is associated with the input.
All 10 inputs can be used as digital inputs, but only some (IN1, IN2, IN3, IN4, IN5, IN6 and IN7 on EV3 HRV; IN1, IN2, IN3, IN4, IN5,
IN9 and IN10 on EVD HRV) can be configured as analogue inputs.
Inputs IN1 and IN2 are universal, configurable through parameters I13 and I14, whereas the other analogue inputs are NTC/digital
inputs.
To configure a digital input, you must assign a number to the corresponding parameter consisting of an absolute value that indicates
the function and a sign that indicates the polarity:
Negative= Normally closed (NC)
Positive= Normally open (NO)
If an unexpected value (see table) is set in parameters I01-I10, the value will not be rejected by the controller, but no function
will be assigned to the input. If two or more inputs are configured with the same value, only the input with the highest index will be
used. For example, if both IN4 and IN6 are configured for a room probe, the value associated with input IN4 will be ignored and only
the value associated with input IN6 will be used.