EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 39 of 74
Label
Default
value
Default
visibility
Min
Max
um
Description
t30
0
U
0
2
Band type for Friday
t31
1
U
0
2
Band type for Saturday
t32
2
U
0
2
Band type for Sunday
t33
16
U
0
100
Holiday end year
t34
1
U
1
12
Holiday end month
t35
1
U
1
31
Holiday end day
t36
0
U
0
23
Holiday end hour
SP
Setpoint Parameters
P01
21.0
U
C02
C01
°C-°F
Temperature setpoint Heating mode Comfort setting
P02
25.0
U
C04
C03
°C-°F
Temperature setpoint Cooling mode Comfort setting
P03
-1.0
U
-12.7
12.7
°C-°F
Temperature offset Heating mode Economy setting
P04
1.0
U
-12.7
12.7
°C-°F
Temperature offset Cooling mode Economy setting
P05
-2.0
U
-12.7
12.7
°C-°F
Temperature offset Heating mode Night setting
P06
2.0
U
-12.7
12.7
°C-°F
Temperature offset Cooling mode Night setting
P07
21.0
U
C02
C01
°C-°F
Temperature setpoint Heating mode Manual setting
P08
25.0
U
C04
C03
°C-°F
Temperature setpoint Cooling mode Manual setting
P09
80
U
C06
C05
%
Fan speed setpoint comfort setting
P10
60
U
C06
C05
%
Fan speed setpoint economy setting
P11
40
U
C06
C05
%
Fan speed setpoint night setting
P12
80
U
C06
C05
%
Fan speed setpoint manual setting
P13
100
U
C06
C05
%
Fan speed setpoint digital input setting
P14
40
U
C08
C07
%
Damper opening setpoint comfort setting
P15
30
U
C08
C07
%
Damper opening setpoint economy setting
P16
20
U
C08
C07
%
Damper opening setpoint night setting
P17
40
U
C08
C07
%
Damper opening setpoint manual setting
CNF
Configuration Parameters
C01
30.0
S
P01
100.0
°C-°F
Maximum Temperature Setpoint Value in Heating Mode
C02
10.0
S
0.0
P01
°C-°F
Minimum Temperature Setpoint Value in Heating Mode
C03
30.0
S
P02
100.0
°C-°F
Maximum Temperature Setpoint Value in Cooling Mode
C04
10.0
S
-10.0
P02
°C-°F
Minimum Temperature Setpoint Value in Cooling Mode
C05
100
S
C06
100
%
Maximum Fan Setpoint Value
C06
10
S
0
C05
%
Minimum Fan Setpoint Value
C07
100
S
C08
100
%
Maximum damper setpoint value
C08
10
S
0
C07
%
Minimum damper setpoint value
C09
1
M
0
1
Enable RTC
0: OFF
1: ON
C10
0
M
-32,768
32,767
Parameter unused
C11
1
S
0
2
Changeover mode
0: Manual
1: Automatic
2: Auto
C12
5
M
1
100
%
Fan/damper control step
C13
10
M
1
255
s
Increase/decrease fan/damper control time
C14
20
M
C06
C05
%
Minimum fan value with compressor ON
C15
20
M
C06
C05
%
Minimum fan value with 1 heater ON
C16
30
M
C06
C05
%
Minimum fan value with 2 heaters ON
C17
30
M
0
255
s
Post-ventilation from OFF
C18
-12
S
-127
127
Servicer password
C19
-123
M
-127
127
Manufacturer password