EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 40 of 74
Label
Default
value
Default
visibility
Min
Max
um
Description
C20
2
S
0
5
Second display
0: Time
1: Humidity
2: Temperature setpoint
3: External temperature
4: Fan speed
5: Fan pressure capacity/differential
C21
0
S
0
1
Sun LED meaning
0: Heating
1: Cooling
C22
1
S
1
247
MODBUS serial address
C23
0
S
0
1
Changeover type configuration
0: Room Temperature
1: External temperature
C24
8
S
0
255
h
Operating Mode Changeover Delay
C25
20.0
S
-10.0
100.0
°C-°F
Temperature for change to heating mode
C26
26.0
S
-10.0
100.0
°C-°F
Temperature for change to cooling mode
C27
0
M
0
2
Type of recovery heat exchanger
0: Cross-flow
1: Rotary
2: Thermodynamic
C28
12
M
0
255
s*10
Minimum compressor off time
C29
36
M
0
255
s*10
Minimum time between compressor switch-ons
C30
2
M
0
2
First coil type
0: Cooling
1: Heating
2: Reversible
C31
20
M
0
100
s
Heater activation period in PWM
C32
10.0
M
0.0
10.0
V
PWM output voltage active
C33
90
M
0
255
s
Three-point Water Valve 1 Running Time
C34
20
M
1
100
Maximum Number of three-point Water Valve Closures for
Re-synchronisation
C35
0
M
-100
100
%
Difference between Supply and Suction
C36
0
M
0
255
s
Fan OFF time for bypass damper
C37
2.0
S
0.0
25.5
°C-°F
Regulation Band in Heating Mode
C38
2.0
S
0.0
25.5
°C-°F
Regulation Band in Cooling Mode
C39
5
M
1
100
%
Heat regulation control step
C40
30
M
1
255
s
Heat regulation increase/decrease time
C41
2.0
M
0.0
25.5
°C-°F
Room temperature delta for follow-on regulation in
Heating mode
C42
2.0
M
0.0
25.5
°C-°F
Room temperature delta for follow-on regulation in
Cooling mode
C43
5.0
M
0.0
25.5
°C-°F
Room Setpoint delta for follow-on regulation in Heating
mode
C44
5.0
M
0.0
25.5
°C-°F
Room Setpoint delta for follow-on regulation in Cooling
mode
C45
3
M
0
3
Dehumidifying mode
0: OFF
1: Heating
2: Cooling
3: Heating/Cooling
C46
50
U
1
100
%
Humidity setpoint