EVCO S.p.A.
EV3 HRV & EVD HRV
| Application manual ver. 1.0a | Code 1443DHRVE104
page 38 of 74
8
CONFIGURING A DEVICE
The following paragraphs list all the possible configurations of the EV3 and EVD HRV devices.
8.1
Parameters
For each parameter a visibility level is assigned that can be modified (only from serial port) with 4 possible values (the visibility value
controls the level of the password to be entered in order to access the relative parameter via the keypad):
0 = Hidden (H)
1 = User (U)
2 = Servicer (S)
3 = Manufacturer (M)
Label
Default
value
Default
visibility
Min
Max
um
Description
TBD
Time Band Parameters
t01
0
U
0
3
Time Band Mode
0: OFF
1: ON
2: Holiday ON
3: Holiday OFF
t02
26
U
0:00
23:45
15 min
Start time band 1 type A
t03
2
U
0
4
Band 1 type A mode
0: Disabled
1: OFF
2: Comfort
3: Economy
4: Night
t04
32
U
0:00
23:45
15 min
Start time band 2 type A
t05
3
U
0
4
Band 2 type A mode
t06
64
U
0:00
23:45
15 min
Start time band 3 type A
t07
2
U
0
4
Band 3 type A mode
t08
84
U
0:00
23:45
15 min
Start time band 4 type A
t09
4
U
0
4
Band 4 type A mode
t10
28
U
0:00
23:45
15 min
Start time band 1 type B
t11
2
U
0
4
Band 1 type B mode
t12
40
U
0:00
23:45
15 min
Start time band 2 type B
t13
3
U
0
4
Band 2 type B mode
t14
64
U
0:00
23:45
15 min
Start time band 3 type B
t15
2
U
0
4
Band 3 type B mode
t16
88
U
0:00
23:45
15 min
Start time band 4 type B
t17
4
U
0
4
Band 4 type B mode
t18
28
U
0:00
23:45
15 min
Start time band 1 type C
t19
2
U
0
4
Band 1 type C mode
t20
40
U
0:00
23:45
15 min
Start time band 2 type C
t21
3
U
0
4
Band 2 type C mode
t22
48
U
0:00
23:45
15 min
Start time band 3 type C
t23
2
U
0
4
Band 3 type C mode
t24
88
U
0:00
23:45
15 min
Start time band 4 type C
t25
4
U
0
4
Band 4 type C mode
t26
0
U
0
2
Band type for Monday
0: Type A
1: Type B
2: Type C
t27
0
U
0
2
Band type for Tuesday
t28
0
U
0
2
Band type for Wednesday
t29
0
U
0
2
Band type for Thursday