Example 1 of EV3K11 electrical connection
Example 1 of electrical connection: EV3K11 is powered by a safety transformer.
N.B.:
-
Do not supply another device with the same transformer
-
The maximum permitted length for connection cables of the INTRABUS port is 30 m (98.4 ft).
Example 2 of electrical connection: EV3K11 is powered by a device.
N.B.:
-
Make sure that the current supplied by the controller is within the limits stated in the TECHNICAL SPECIFICATIONS section
-
The maximum permitted length for connection cables of the INTRABUS port is 10 m (32.8 ft).