4.1.9. Install isolation switch (only for Singapore)
When the charging station is installed in Singapore, an isolation switch must be installed in the power
supply wiring to ensure compliance with Singapore SS CP 5 Clause 463 rules.
The isolation switch must have the following characteristics:
• A utilisation category of at least AC22A in accordance with IEC 60947-3.
• An IP54 or better enclosure rating.
• A 16 A or 32 A rating to match the charging station connection capacity.
• The switch knob must be red.
• All phases and neutral must be switched.
• The PE/G connection can use a terminal block connection.
The isolation switch must be installed in a location that is easily accessible when using the charging
station.
The following wiring diagrams are examples of the wiring connections to the isolation switch.
1 phase connection
3 phase connection
4.2. Unpacking
See the corresponding illustrations in manual B.
1.
Open the package marked with the charging station then remove the packaging holding the
accessories folder.
2.
Remove the accessories folder from the packaging.
Note:
Keep the packaging to use as the drilling template when installing the wall dock.
3.
Lift out the station.
4.
Lift out the wall dock.
5.
Remove the cardboard filler from the wall dock.
EN
4. Installation instructions
18