background image

8

Operation and Maintenance Instructions

Variable Frequency Drive Lock-out Notification

 WARNING:  Qualified personnel should use proper care, 

procedures and tools when maintaining 

the Fan/Drive System in order to prevent 

personal injury and/or property damage.

 WARNING:   Identify and Lock-out Harmful Resonant 

Frequencies

A Variable Frequency Drive (VFD) fan system, unlike traditional 

fixed-speed systems, is designed to operate between 25% 

(15Hz) and 100% (60Hz) speeds, which creates an opportunity 
for operation where resonant frequencies exist. Sustained op-
eration at resonant frequencies may lead to excessive vibration, 
fatigue of structural components and/or drive system noise and 
failure. Owners and operators must anticipate the existence of 
resonant frequencies and lock out frequencies during start-up 
and commissioning in order to prevent drive system operational 
problems and structural damage. As a part of the normal start-
up and commission processes, resonant frequencies should be 

identified and locked-out in the VFD’s software.

The unit’s supporting structure, external piping, and accesso-
ries contribute to the overall harmonic make-up and stiffness 

of the system. The choice of VFD will also have a significant 
influence on how the system behaves. Consequently, not all 

resonant frequencies can be determined in advance at the 

manufacturer’s factory during final inspection and testing. Rel

-

evant resonant frequencies (if they occur) can only be identi-

fied accurately after the installation in the system.

To check for resonant frequencies in the field, a run-up and 

run-down test must be performed. Additionally, VFD carrier 
frequencies should be adjusted to best align the VFD with the 
electrical system. Refer to your drive’s start-up procedures for 
additional information and instruction.

The procedure of checking for resonant frequencies requires 
stepping through the VFD’s operating range at (2) Hz intervals 
from the lowest operating frequency to full speed. At each step, 
pause long enough for the fan to reach steady-state. Note 
changes in unit vibration during this time. Repeat from full speed 
to minimum speed. Should vibration-inducing frequencies exist, 
the run-up and run-down test will isolate the resonant frequencies 
which then must then be locked-out in the VFD programming.

Two-Speed Motors

The use of a two-speed motor provides an additional step of 
capacity control when used with the fan cycling method. The 
low speed of the motor will provide approximately 60% of full 
speed capacity.

Two-speed capacity control systems require not only a two-
speed motor, but also a two-stage thermostat and the proper 
two-speed motor starter. The most common two-speed motor 
is a single winding type. This is also known as a consequent 
pole design. Two-speed two-winding motors are also 
available. All multi-speed motors used in evaporative cooling 
units should be variable torque design.

NOTE: When two-speed motors are to be used, the motor 
starter controls must be equipped with a decelerating time 
delay relay. The time delay should be a minimum of 30 
seconds when switching from high speed to low speed.

Sequence of Operations / Guidelines for Multi-fan Units 

with a VFD during Peak Load

For eco-ATWE, see Sage

2

/Sage

3

 control Panel O&M:

1.  Both fan motors off – Pump running on one cell.
2.  Both fan motors off – Pump running on both cells.
3.  One fan motor on low speed, one fan motor off – Pump 

running on both cells.

4.  Both fan motors on low speed – Pump running on both 

cells.

5.  One fan motor on high speed, one fan motor on low speed 

– Pump running on both cells.

6.  Both fan motors on full speed – Pump running on both 

cells.

Recirculated Water System - 

Routine Maintenance

Suction Strainer in Cold Water Basin

The pan strainer should be removed and cleaned monthly 
or as often as necessary. Make certain that the strainer is 
properly located over the pump suction, alongside the anti-
vortexing hood.

Cold Water Basin

The cold water basin should be flushed out quarterly, and 
checked monthly or more often if necessary, to remove any 
accumulation of dirt or sediment which normally collects 
in the basin. Sediment can become corrosive and cause 
deterioration of basin materials. When flushing the basin, it is 
important to keep the suction strainers in place to prevent any 
sediment from entering the system. After the basin has been 
cleaned, the strainers should be removed and cleaned before 
refilling the basin with fresh water.

Summary of Contents for ATC-E

Page 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Page 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Page 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Page 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Page 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Page 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Page 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Page 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Page 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Page 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Page 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Page 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Page 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Page 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Page 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Page 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Page 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Page 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Page 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Page 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Reviews: