background image

15

Operation and Maintenance Instructions

Unit Accessories

 

The appropriate accessories to prevent or minimize ice 
formation during cold weather operation are relatively simple 
and inexpensive. These accessories include cold water 
basin heaters, the use of a remote sump, electric water level 
control and vibration cut out switches. Each of these optional 
accessories ensures that the cooler or condenser will function 
properly during cold weather operation. 

Cold Water Basin Heaters

 

Optional basin heaters can be furnished with the unit to 
prevent the water from freezing in the basin when the 
unit is idle during low ambient conditions. The basin 
heaters are designed to maintain 40°F (4°C) basin water 
temperature at a 0°F (-18°C) ambient temperature. The 
heaters are only energized when the recirculating pumps 
are off and no water is flowing over the heat exchanger 
coil. As long as there is a heat load and water is flowing 
over the heat exchanger coil, the heaters do not need to 
operate. Other types of basin heaters to consider would 
include:  hot water coils, steam coils or steam injectors. 

Remote Sumps

 

A remote sump located in an indoor heated space is an 
excellent way to prevent freezing in the cold water basin 
during idle or no load conditions because the basin and 
associated piping will drain by gravity whenever the 
recirculating pump is idle. EVAPCO units built for remote 
sump operation do not include recirculating water pumps. 

Electric Water Level Control

 

Optional electric water level control packages can be 
furnished to replace the standard mechanical float and 
valve assembly. The makeup water pressure for electronic 
water level control should be maintained between 5 and 
100 psig (35 and 690 kPa). The electric water level control 
eliminates the freezing problems experienced by the 
mechanical float. In addition, it provides accurate control of 
the basin water level and does not require field adjustment 
even under varying load conditions. Please note:  the 
standpipe assembly, make up piping and solenoid valve 
must be heat traced and insulated to prevent them from 
freezing. 

Vibration Cut Out Switches

 

During severe cold weather conditions, ice can form on 
the fans of cooling towers causing excessive vibration. 
The optional vibration switch shuts the fan off avoiding 
potential damage to or failure of the drive system. 

Capacity Control Methods for Cold Weather 

Operation

 

Induced draft and forced draft coolers or condensers require 
separate guidelines for capacity control during cold weather 
operation. 

The sequence of control for a unit operating at low ambient 
conditions is much the same as a cooler or condenser 
operating under summer conditions provided that the 
ambient temperature is above freezing. When the ambient 
temperatures are below freezing, additional precautions must 
be taken to avoid the potential for damaging ice formation. 

The most effective way to avoid ice formation in and on a 
closed circuit cooler or condenser during the winter is to 
run the unit DRY. In dry operation, the recirculation pump is 
turned off, the basin drained, and air passes over the coil. 
Instead of using evaporative cooling to cool the process fluid 
or condense the refrigerant, sensible heat transfer is utilized, 
so there is no recirculation water to freeze. If this method will 
be used on a forced draft unit, be sure to verify that the motor 
and drives have been properly sized to handle the reduction 
in static pressure experienced when the spray water is turned 
off.

It is very important to maintain close control of the cooler or 
condenser during winter operation. EVAPCO recommends 
that an absolute MINIMUM leaving water temperature of 42° 
F (6°C) must be maintained for cooler applications. The higher 
the leaving temperature from the cooler or condenser, the 
lower the potential for ice formation. 

Induced Draft Unit Capacity Control

 

The simplest method of capacity control is cycling the 
fan motor on and off in response to the leaving fluid 
temperature of the cooler or condenser. However, this 
method of control results in larger temperature differentials 
and longer periods of down time. During extremely low 
ambient conditions, the moist air may condense and freeze 
on the fan drive system. Therefore, fans must be cycled 
during extremely low ambient conditions to avoid long 
periods of idle time when water is flowing over the coil. The 
number of start/stop cycles must be limited to no more 
than six per hour. 

A better method of control is the use of two-speed fan 
motors. This allows an additional step of capacity control. 
This additional step reduces the water temperature 
differential, and therefore, the amount of time the fans 
are off. In addition, two-speed motors provide savings 
in energy costs, since the cooler or condenser has the 
potential to operate on low speed for the reduced load 
requirements. 

The best method of capacity control during cold weather 
operation is the use of a variable frequency drive (VFD). 
This allows the closest control of the leaving water 
temperature by allowing the fan(s) to run at the appropriate 
speed to closely match the building load. As the building 
load decreases, the VFD control system may operate for 
long periods of time at fan speeds below 50%. Operating a 
low leaving water temperature and low air velocity through 
the unit can cause ice to form. It is recommended that the 
minimum speed of the VFD be set at 50% of full speed to 
minimize the potential for ice to form in the unit. 

Forced Draft Unit Capacity Control 

The most common methods of capacity control are cycling 
the single speed fan motors, using two-speed motors 
or pony motors and utilizing variable frequency drives to 
control the cooler or condenser fans. Although capacity 
control methods for forced draft units are similar to those 
used for induced draft units, there are slight variations. 

The simplest method of capacity control for forced draft 
units is to cycle the fan(s) on and off. However, this 
method of control results in larger temperature differentials 
and periods of time with the fans off. When the fans are 
cycled off, the water falling through the unit can draw air 

Summary of Contents for ATC-E

Page 1: ...Box 1300 Westminster Maryland 21158 USA Phone 410 756 2600 Fax 410 756 6450 EVAPCO Europe bvba Heersterveldweg 19 Industrieterrein Oost 3700 Tongeren Belgium Phone 32 12 395029 Fax 32 12 238527 evapc...

Page 2: ...A lock out tag out procedure integrated with the Process Control System must be foreseen by the customer A lockable disconnect switch should be located within sight of the unit for each fan motor ass...

Page 3: ...could potentially cause damage to plastic components Label on the coil section s WARNING Do not operate the pressure vessel at service conditions outside of the PED nameplate located at the coil conne...

Page 4: ...d minimum speeds and for recommendations on locking out resonance frequencies 5 Verify that a water treatment plan has been implemented including passivation of galvanized steel units See Water Treatm...

Page 5: ...e fully opened before the pumps turn on If the system temperature continues to rise the unit fan is cycled on For a variable speed controller the fans are turned on to minimum speed See the Fan System...

Page 6: ...38 C Regal R O 220 DTE Oil BB Teresstic 220 All bearings used on EVAPCO equipment are factory adjusted and self aligning Do not disturb bearing alignment by tightening the sleeve bearing caps Fan Bel...

Page 7: ...if operating below 25 is possible NOTE Pump Motors VFD s should not be used on pump motors The pumps are designed to be operated at full speed and are not intended to be used as capacity control The t...

Page 8: ...to minimum speed Should vibration inducing frequencies exist the run up and run down test will isolate the resonant frequencies which then must then be locked out in the VFD programming Two Speed Moto...

Page 9: ...e is a bronze valve connected to a float arm assembly and is activated by a large foam filled plastic float The float is mounted on an all thread rod held in place by wing nuts The water level in the...

Page 10: ...p When Supplied The pump and pump motor should be lubricated and serviced in accordance with the pump manufacturer s instructions The recirculation pump should not be used as a means of capacity contr...

Page 11: ...f operation During this passivation period recirculating water pH should be maintained above 7 0 and below 8 0 at all times Since elevated temperatures have a harmful effect on the passivation process...

Page 12: ...oling equipment can be considered as long as the resultant recirculating water chemistry conforms to the parameters noted in Table 3 It should be noted that using water reclaimed from other processes...

Page 13: ...10 x24 20 x12 10 x18 10 x36 20 x18 12 x12 12 x14 12 x18 12 x24 12x28 12 x36 24 x12 24 x14 24 x18 24 x24 24 x28 24 x36 12 x20 12 x40 24 x20 24 x40 2 0 2 0 2 0 2 0 3 0 4 0 2 5 2 5 3 7 5 7 3 5 2 5 3 0 2...

Page 14: ...ith a remote sump is an excellent way of reducing unit capacity at low temperatures Other methods of capacity control include two speed motors VFDs and fan cycling These can be used individually or in...

Page 15: ...ser during the winter is to run the unit DRY In dry operation the recirculation pump is turned off the basin drained and air passes over the coil Instead of using evaporative cooling to cool the proce...

Page 16: ...ethod of managing the amount of ice buildup is by cycling the fan motors off while keeping the pump on During these periods of idle fan operation the warm water that is absorbing the building load flo...

Page 17: ...crape and coat with ZRC annually 10 Lubricate fan shaft bearings every 1000 hours of opera tion or every three months 11 Lubricate fan motor bearings see mfg s instructions Typi cally for non sealed b...

Page 18: ...robe ends of scale build up quarterly 12 Electronic Water Level Controller Clean inside the standpipe annually 13 Solenoid Make up Valve Inspect and clean valve of debris as needed 14 Vibration Switch...

Page 19: ...ned at least once a month by hand This can be accomplished by making sure the unit s disconnect is tagged and locked out and grasping the fan assembly rotating it several turns 9 Energize fan motor sp...

Page 20: ...2013 EVAPCO Europe Bulletin 116R E Metric 0322 Operation and Maintenance Instructions...

Reviews: